Appendix a – AERCO KC1000 Low NOx Water Heater July 2011 User Manual

Page 82

Advertising
background image

APPENDIX A

A-4

APPENDIX A -

WATER HEATER MENU ITEM DESCRIPTIONS - Continued

MENU LEVEL & OPTION

DESCRIPTION

TUNING MENU

Prop Band

Generates a valve position based on the error that

exists between the setpoint temperature and the

actual outlet temperature. If the actual error is less

than the proportional band setting (1 to 120°F), the

valve position will be less than 100%. If the error is

equal to or greater than the proportional band

setting, the valve position will be 100%.

Integral Gain

This sets the fraction of the output, due to setpoint

error, to add or subtract from the output each minute

to move towards the setpoint. Gain is adjustable

from 0.00 to 1.00 (Default is 0.10).

Derivative Time

This value (0.0 to 20.0 min.) responds to the rate of

change of the setpoint error. This is the time that

this action advances the output.

Min Load Adj

Setting is adjustable from -50°F to +50°F (Default is

zero). It adjusts the output by adding an offset to

the breakpoint chart at minimum flow. This is used

to fine tune Feed-Forward (FFWD) output at low

flow levels.

Max Load Adj

Setting is adjustable from -50°F to +50°F (Default is

zero). It adjusts the output by changing the scaling

of the breakpoint chart at maximum flow.

FFWD Temp

Displays the Feed-Forward temperature.

Outlet Feedback

Used to Enable or Disable feedback. Disable this

function for Feed-Forward control only.

Feedback Gain*

Adjustable from 0.01 to 1.00 (Default is 0.05).

Breakpoint at 100%

Thru

Breakpoint at 0%

Allows breakpoint temperature settings (30°F to

240°F) to be entered for 100% to 0% in 10%

increments. See Appendix D for default values.

Reset Defaults?

Allows Tuning Menu options to be reset to their

Factory Default values.

*Only displayed when Heater Tuning Display is enabled by factory authorized

personnel.