APPENDIX A

A-1

APPENDIX A -

WATER HEATER MENU ITEM DESCRIPTIONS

MENU LEVEL & OPTION

DESCRIPTION

OPERATING MENU

Active Setpoint

This is the setpoint temperature to which the

control is set when operating in the Constant

Setpoint or Remote Setpoint Mode. When in the

Constant Setpoint Mode, this value is equal to the

Internal Setpoint setting in the Configuration Menu.

When in the Remote Setpoint Mode, this value is

the setpoint equivalent to the remote analog signal

supplied to the unit

Air Temp

For monitoring purposes only

Outdoor Temp

Displayed only if outdoor sensor is installed and

enabled.

Valve Position In

Desired input valve position. This would normally

be the same as the valve position shown on the

bargraph when the heater is operating.

Flame Strength

Displays flame strength from 0% to 100%.

Run Cycles

Displays the total number of run cycles from 0 to

999,999.

Run Hours

Displays total run time of unit in hours from 0 to

9,999,999.

Fault Log

Displays information on the last 20 faults (0 – 19).

SETUP MENU

Password

Allows password to be entered.

Once the valid password (159) is entered, options

in the Setup, Configuration and Tuning Menus can

be modified.

Language

English only

Time

Displays time from 12:00 am to 11:59 pm.

Date

Displays dates from 01/01/00 to 12/31/99

Unit of Temp

Permits selection of temperature displays in

degrees Fahrenheit (°F) or degrees Celsius (°C).

Default is °F.

Comm Address

For RS-485 communications (0 to 127). Default

address is 0. RS-232 should have its own

(programmable) password.

Baud Rate

Allows communications Baud Rate to be set (2400

to 19.2K). Default is 9600.

Software Version

Identifies the current software version of the

control box (Ver 0.0 to Ver 9.9).