BASO VLV49A Series User Manual

Page 12

Advertising
background image

12 VLV49A Series Universal Replacement Gas Valve Technical Bulletin

!

WARNING: Fire or Explosion Hazard. Avoid personal injury

or property damage by making sure the valve
functions properly and there are no gas leaks.
Follow this checkout procedure before leaving the
installation.

Make sure all components are functioning properly by performing the
following test:

1. Test for leaks on all pipe joints and connections upstream of the gas

valve with a soap solution.

2. Turn the thermostat to a low setting.

3. Turn on the gas and purge the gas lines of all air.

4. Turn the thermostat to a high setting. The appliance should operate in

accordance with the manufacturer’s specified sequence of operation.

5. Test for leaks on all pipe joints and connections downstream of the

gas valve with a soap solution.

6. Turn the thermostat down for at least 30 seconds and then back up

again. Verify successful ignition at least three times before leaving
the installation.

The VLV49A replacement valves are not field repairable. Do not
attempt field repairs. For a replacement valve, contact the nearest
BASO Gas Products distributor.

Checkout
Procedure

Repairs and
Replacement

1007 South 12th Street
PO Box 170
Watertown, WI 53094

www.baso.com

1-877-227-6427 (1-877-BASOGAS)

Printed in U.S.A.

Advertising