Installation Instructions (cont’d)

Filling the Water Heater

A CAUTION

Never use this water heater unless it is completeiy filied with
water. 1b prevent damage to the tank, the tank must be liiled
with vrater. Water must flow from the hot water faucet
before turning "ON” gas to the water heater.

To fill the water heater with water:

Close the water heater drain valve by turning the handle to

the right (clockwise). The drain valve is on the lower firont of
the water heater,

• Open the cold water supply valve to the water heater.

NOTE: The cold water supply valve must be left open
when ¿e water heater is in use.

To insure complete filling of the tank, allow air to exit by

opening the nearest hot water faucet. Allow water to run
until a constant fiow is obtained. This will let air out of the
water heater and the piping.

• Check all new water piping for leaks. Repair as needed.

Venting

AWARNING

VENT DAMPERS - Any vent damper, whether it is operated
thermally or otherwise must be remov^ if its use inhibits prop­
er drafting of the water heater.
Thermally Operated Vbnt Dampers: Gas-fired water heaters

hawing thermal efficiency in excess of 80% may produce a rela­
tively kw flue gas temperature. Such temperatures may not be

high enough to properly open thermally operated vent

dampers. This would cause spillage of flue gases and may cause

carbon monoxide poisoning.

>fent dampers must bear evidence of certification as complying
with the latest edition of American National Standard ANSI
Z2I.68 (ANSI Z2I.66 & 67, respective, cover electrically and

mechanically actuated vent danripers). ElA>re installation of any

vent damper, consult your local Sevs Serdce Center or the gas

utility for further infomation.

AWARNING

To insure proper venting of this gas-fired water heater, the
correct vent pipe diameter must be utilized. Any additions or
deletions of other gas appliances on a common vent with this
water heater may advenety affect the operation of the water

heater. Consult the local Sears Service Center or gas utility if
any such changes are planned.

For proper venting in certain installations, a larger diameter vent
pipe may be necessary. Due to great variances in installations,
unforeseeable by the manufiicturer of the water heater, you must
consult your gas company to aid you in determining the proper
venting for your water heater from the vent tables m the latest
edition of the National Fuel Gas Code ANSI Z223.1, also
referred to as NFPA 54.

Check the venting system for signs of obstruction or deteriora­
tion and replace if needed.

The combustion and ventilation air flow must not be obstructed.

AWARNING

Obstructed or deteriorated vent systems may present a serious
health risk or asphyxiation.

Place the draft hood legs in the receiving holes on the top of
the water heater. The legs wiU snap in the holes to give a tight
fit.
Place the vent pipe over the draft hood. With the vent pipe in
position, drill a small hole through both the vent pipe and
draft hood. Secure them together with a sheet metal screw.

DRAFT HOOD ^

VENT,
SCRE

'si I

4

'

DRAFT HOOD

DRAFT

VENT TO OUTDOORS OR

CHJMNEY

AWARNING

The water heater with draft hood installed must be properly
vented to a chimney which terminates outdoors. Never opei^
ate the water heater unless it is vented to the outdoors and has
adeqw^ air supply to avoid risks of improper operation, explo­
sion or asphyxiation.

AWARNING

The vent pipe from the water heater must be no less than the
diameter of the draft hibod outlet on the water heater, and
must slope upward to the chimney at least inch per linear
foot

13