TROUBLESHOOTING

Start Up Conditions

THERMAL EXPANSION

CAUTION

Property Damage Hazard

' Avoid water heater damage.

' Install thermal expansion tank or device if necessary.

' Contact qualified installer or service agency.

As water is heated, it expands (thermal expansion). In a closed
system, the volume of water will grow. As the volume of water
grows, there will be a corresponding increase in water pressure
due to thermal expansion. Thermal expansion can cause

premature tank failure (leakage). This type of failure is not
covered under the limited warranty. Thermal expansion can also
cause intermittent temperature-pressure relief valve operation:

water discharged from the valve due to excessive pressure build

up. The temperature-pressure relief valve is not intended for the
constant relief of thermal expansion. This condition is not covered
under the limited warranty.

A properly-sized thermal expansion tank should be installed
on all closed systems to control the harmful effects of thermal
expansion. Thermal expansion tanks are available from Sears
stores and through the Sears Service Centers. Contact the local

plumbing inspector, water supplier and/or the Sears Service
Center for assistance in controlling these situations.

Table 3: Thermal Expansion Tank Specifications

Model

Number

Tank

Capacity

In Gaffons

Dimensions

in Inches

Pipe

Fitting

On Tank

Diameter

Length

153.331020

2

8 (203 mm)

12-3/4” (323 mm)

3/4” Male

153.331050

5

11 (279 mm)

14-3/4” (375 mm)

3/4” Male

Table 4: Expansion Tank Sizing Chart

Expansion

Tank

Capacity

Needed

Inlet*

Water

Pressure

Water Heater Capacity

(Gallon)

30

40

50

66

82

40psi

2

2

2

5

5

50psi

2

2

2

5

5

60psi

2

2

5

5

5

70psi

2

2

5

5

5

SOpsi

2

5

5

5

5

‘Highest recorded inlet water pressure in a 24 hour period or
regulated water pressure.

NOTE: Expansion tanks are pre-charged with a 40 psi air
charge. If the inlet water pressure is higher than 40 psi, the

expansion tank’s air pressure must be adjusted to match
that pressure, but must not be higher than 80 psi.

6 INCH T

MAXIMUM AIR GAP ♦ cl

WATER HEATER

COLD WATER

INLET FITTING

WATER HEATER
COLD WATER
INLET FITTING

PRESSURE GAUGE' INLET COLD

WATER

SHUTOFF

RECOMMENDED INSTALLATION

(VERTICAL MOUNTING)

FLOOR, CEILING

JOIST, ETC.

FIGURE 22.

STRANGE SOUNDS
Possible noises due to expansion and contraction of some metal
parts during periods of heat-up and cool-down do not represent
harmful or dangerous conditions.

Operational Conditions____________________

POWERED ANODE ROD OPERATION

To shelter the glass-lined water tank from corrosion through

electrolysis, this water heater is equipped with a non-sacrificial

powered anode which should not need to be replaced under

normal operating conditions. NOTE: The powered anode oper­

ates only when electrical power is applied.

If the powered anode malfunctions it should be replaced by a

qualified technician.

IMPORTANT: If a faulty powered anode is not repaired or has

been removed permanently, then all warranties are void.

21