Auto. Restart After Power Failure

This option may be enabled or disabled, and may be viewed/modified in the Config table of

Equipment Configuration. If enabled, the chiller will start up automatically after a single cycle

drop-out, low, high, or loss of voltage has occurred, and the power is within ±10% of normal.

The 15-min start-to-start timer and the stop-to-start timer are ignored during this type of start-up.

When power is restored after the power failure, and if the compressor had been running, the

oil pump will be energized for one minute prior to the evaporator pump energizing. Auto restart

will then continue like a normal start-up.

IMPORTANT: Afield-supplied water temperature control system for condenser
water should be installed. The system should maintain the leaving condenser water
temperature at a temperature that is 20° F (11° C) above the leaving chilled water
temperature.

CAUTION

CAUTION

!

The tower-fan relay control is not a substitute for a condenser water temperature
control. When used with a Water Temperature Control system, the tower fan
relay control can be used to help prevent low condenser water temperatures and
associated problems.