14 - Configuring Read-Only Ethernet TCP/IP Devices

DeviceMaster UP EtherNet/IP Quick Start: 2000478 Rev. D

Configuring Read-Only Ethernet TCP/IP Devices

3.

Click the appropriate Socket N link to open Edit Socket Port Configuration page.

4.

Under Device TCP Connection
Configuration
, select Enable and
configure the port for your environment.

If your Ethernet TCP/IP device
requires another device to connect to
it, configure the socket port on the
DeviceMaster UP to Connect mode.

-

Do not enable the Listen option.

-

Set Connect To Mode to Connect-
Always
.

-

Set the Connect Port to the socket
port number of your Ethernet device.

-

Set the Connect IP Address to the IP address of your Ethernet device.

-

Set Disconnect Mode to Never.

If your Ethernet TCP/IP device is
configured to connect to another
device, configure the socket port on
the DeviceMaster UP to Listen mode.

-

Select Listen.

-

Use the default Listen Port on the
DeviceMaster UP of 8xxx or
designate your own.

-

Set Connect To Mode to Never.

-

Set Disconnect Mode to Never.

-

Configure your Ethernet device to connect to the DeviceMaster UP at the DeviceMaster UP IP
address
and Listen Port.

If you do not know if your device will
connect to another Ethernet device,
but do know your device’s socket port
and IP address, you can do the
following to enable both the Listen and
Connect modes:

-

Select Listen.

-

Use the default Listen Port on the
DeviceMaster UP of 8xxx or
designate your own.

-

Set Connect To Mode to Connect-
Always
.

-

Set the Connect Port to the port number of your Ethernet device.