DeviceMaster UP EtherNet/IP Quick Start: 2000478 Rev. D

Configuring Read/Write Devices - 21

Configuring Read/Write Devices

6.

Add the transmit message to your PLC program. It may help to reference rung 3 of
loopbackExampleTagWrite.L5K.

7.

Open the transmit message.

8.

On the Configuration Controller pane:

Set Message Type to CIP Generic.

Set Service Type to Set Attribute Single.

Set Class to:

-

Serial ports: Set to 71 Hex.

-

Socket ports: Set to 74 Hex.

Set Instance to the serial or socket number.

Set Attribute to 1.

Set Source Element to Com1_TxDataStr (or
Skt1_TxDataStr).

Set Source Length to at least the length
TxDataStr.length (or Skt1_TxDataStr.length)
plus 4.

9.

On the Communication pane:

Set Path to: <Ethernet IP Card Name>,2,<IP
Address>.

Leave Connected unchecked.

Click OK.

10. Add controlling logic to your PLC program to

control when to transmit the message. You may
wish to use loopbackExampleTagWrite.L5K as a
reference.