START--UP AND OPERATION

Step 1

—Checking Air Purifier Operation

ELECTRICAL SHOCK AND HIGH VOLTAGE

HAZARD
Failure to follow this warning could result in personal injury

or death.
Before installing or servicing system, always turn off main

power to system. There may be more than one (1) disconnect

switch.

!

WARNING

a. Attach the Infinityt Air Purifier door to the cabinet. A

magnet in the door (see Fig. 8) is used to activate a safety

switch in the power supply when the door is installed. The

power supply will not energize the air purifier unless the

safety switch is activated.

b. Turn the HVAC system power on and adjust the thermo-

stat or Infinityt System Control to activate the system

fan.

c. Turn the Infinityt Air Purifier power switch to on posi-

tion.

d. The power indicator light above the Air Purifier power

switch should illuminate (see Fig. 13).

e. Check to ensure the light goes off when the Infinityt Air

Purifier power switch is set to off, when the blower goes

off, or when the HVAC system power is turned off.

NOTE:

Upon power--up, the light will come on for

approximately 5 seconds and if no flow is detected, it will go off.

If no air purifier cartridge is detected, the flow sensor will detect

this and turn off after approximately 7 seconds.
Step 2

—Infinity Control
a. When the Infinityt Air Purifier is used with an Infinity

Control, the Infinity Control can be configured to remind

the homeowner when it is time to change the Infinityt

Air Purifier cartridge. This maintenance reminder can be

based on either the TrueSenset dirty filter algorithm or

time. The installer should use their discretion to select the

most appropriate option based on the initial system static

pressure.

Step 3

—Maximizing Performance
a. Maximum air purification performance is obtained when

the furnace blower is set for continuous operation on the

thermostat or Infinity Control.

Door Switch Magnet

A06379

Fig. 12

--- Door Switch Magnet

Power Indicator

A06380

Fig. 13

--- Power Indicator

MAINTENANCE

The Infinity t Air Purifier is designed to require minimal

maintenance. Maintenance is limited to the replacement of the

air purification cartridge and inspection/brush cleaning of the

ionization array. Frequency of air purifier cartridge replacement

and cleaning of the ionization array may vary depending on

ductwork design and local environmental conditions.
To replace the air purifier cartridge, complete the following
steps:
Step 1

—Turn the heating and cooling system power

off.

ELECTRICAL SHOCK AND HIGH VOLTAGE

HAZARD
Failure to follow this warning could result in personal injury

or death.
Before installing or servicing system, always turn off main

power to system. There may be more than one (1) disconnect

switch.

!

WARNING

Step 2

Turn the Infinityt Air Purifier switch to the off

position.
Step 3

Remove the Infinityt Air Purifier door.

Step 4

Slide out the old air purifier cartridge and discard.

Step 5

Install the new air purifier cartridge.

NOTE: Make sure that the arrows on the air purifier cartridge

point toward the fan coil. This should be in the same
direction as airflow.

Step 6

Replace the Infinityt Air Purifier door.

Step 7

Turn the Infinityt Air Purifier switch to the on

position.
Step 8

Turn heating and cooling system power on.