MAC 10 ORIGINAL VE5 SERVICE MANUAL

PAGE 22

readings (128 velocity points). Envirco recognized using eight reading during a

cleanroom start-up may be time consuming and recommends using three Velgrid

readings taken on a diagonal, as shown below.

Figure 12- Velgrid Testing

Recommended Testing – 8 readings with a Velgrid

Factory Approved Testing – 3 readings with a Velgrid

Some of the testing procedures performed on the MAC 10 VE5 include PSL challenge

of HEPA/ULPA filters to assure specified performance, along with air velocity

measurement and adjustment tests. No DOP is used on Mac 10 Filters, unless

requested.

Recommended Testing

All units that are airflow tested at Envirco are tested using a Shortridge Airdata

Multimeter 800 series with a Velgrid head. The recommended method of

reading is to place one corner of the Velgrid head 1-1/4” from the corner of the

filter face and then take four reading evenly spaced along the four foot side, then

repeat these reads for the other long side. This gives a total of eight reading to

test the unit. All advertised data is based on using the Velgrid with eight