5.2.3

Reader Daisy-Chain

One Proximity reader is shared by all elevator control panels in an elevator control application. The
main reader connections are made to a primary LC-502P elevator panel. All other reader
connections to the remaining LC-502P/LC-508P panels are made per the following rules.

1. The reader antenna line must be daisy-chained to all other elevator panel antenna inputs – Pin 1

of TB-5 and TB-6 on the LC-502P/LC-508P panels.

2. The reader ground line must be daisy-chained to all other elevator panel antenna grounds to

provide a standard ground reference for all panels – Pin 4 of TB-5 and TB-6 on the LC-502P/
LC-508P panels.

3. The reader’s positive power line must be connected to the master elevator panel ONLY (Pin 3 of

TB-5 on the master LC-502P/LC-508P panel).

Make the reader connections per the information in Figure 8 on page 14.