3.7

Cable Requirements

RS-232 Serial Cable
-

four conductor (for direct connect) or five conductor (for modem connection), shielded,
stranded AWG 24 wire (Belden 9534 or a heavier gauge)

-

50 foot maximum length (per RS-232 industry specification – greater lengths are not
recommended)

RS-485 Network Cable
-

two conductor, shielded, twisted pair, stranded, AWG 24 wire (Belden 9501 or a larger
gauge)

-

16,000 foot total network length

-

refer to the Network Wiring Application Note (P/N 01824-002) for specific network wiring
information

Input Power
-

two conductor, stranded, AWG 18 wire (Belden 8461 or a heavier gauge)

-

200 foot maximum length

NOTE: On long power cable runs, the cable resistance causes a drop in voltage at the end of the
cable run. Be sure your power supply provides 12 VDC at the end of the cable run.

Reader to Panel
-

six conductor, shielded, stranded AWG 24 wire (Belden 9536 or a heavier gauge)

Output Connections
-

two conductor, stranded AWG 22 (Belden 9532 or a heavier gauge)

NOTE: The Floor Control Relay may require a heavier gauge of wire depending upon the current
demands of the elevator panel and the length of the wiring run.

NOTE: If plenum cable is required, please reference the Belden equivalent to the cable listed above.