2 do not, Proximity elevator control panel – Keri Systems LC-508 Proximity Elevator Control User Manual

Page 6

Advertising
background image

Proximity Elevator Control Panel

2305 Bering Drive

01941-001 Rev. B

San Jose, CA 95131 USA
(800) 260-5265 (408) 435-8400 FAX (408) 577-1792
Web: www.kerisys.com E-mail: [email protected]

Page 6 of 22

Quick S

tart Guide

LC-502P/LC-508P

4.2

Do Not

Make modem phone line connections through PBX telephone switching systems - most
modems are not compatible with PBX systems leading to disconnection problems with the
modem.

Locate a LC-500P controller near EMI sources - EMI sources can affect the performance of the
controller.

Locate a reader near EMI sources - EMI sources can affect the performance of the reader.

Use non-approved switching power supplies, or high noise/high ripple current - they are EMI
sources.

Route network and reader cables beside power cables - transients on the power cables may be
picked-up by network and reader cables.

Stretch or over-tension cables.

Route cables over sharp objects.

Let the cables get tangled.

Mix LC-500Ps with PXL-100s in the same network.

Connect earth ground to the network cable shield - the LC-500P automatically connects earth
ground to the shield at one point on the network to prevent ground loops.

Use gender changer plugs when making RS-232 serial communication connections (unless you
know it is a "straight-through" plug) - gender changers may have internal wiring changes that
can disrupt communications.

Advertising
This manual is related to the following products: