Specifications continued-

Table 4: Water Heater Performance




MODEL

Maximum First

Hour Rating

(Gal/Hr) @

140 °F 115 °F

Continuous

Draw Rating

(Gal/Min) @

140 °F 115 °F

Approximate

Boiler Output

Needed For

Ratings

(BTU/hr)

30-Gal. / Res.

279 429 4.2 6.7

220,000

40-Gal. / Res.

288 438 4.2 6.7

220,000

40-Gal. “R” / Res.

288 438 4.2 6.7

220,000

50-Gal. / Res.

297 447 4.2 6.7

220,000

50-Gal. “R” / Res.

297 447 4.2 6.7

220,000

65-Gal. / Res.

306 456 4.2 6.7

220,000

65-Gal. / Com.

534 820 8.0 12.8 420,000

80-Gal. / Res.

321 470 4.2 6.7

220,000

80-Gal. / Com.

546 834 8.0 12.8 420,000

120-Gal. / Res.

357 507 4.2 6.7

220,000

120-Gal. / Com.

583 871 8.0 12.8 420,000

NOTES: Based on 200 °F boiler water temperature and 50 °F potable
water inlet temperature.

Table 5: Water Heater Performance



MODEL

Hot Water

Availability

(Minutes)

Coil Heat

Transfer Area

(Sq Ft)

Pressure Drop at

Rated Heat Source

Flow Rate

(Feet of Head)

30-Gal. / Res.

5.5

14.2

1.5

40-Gal. / Res.

7.5

14.2

1.5

40-Gal. “R” / Res.

7.5

14.2

1.5

50-Gal. / Res.

9.0

14.2

1.5

50-Gal. “R” / Res.

9.0

14.2

1.5

65-Gal. / Res.

11.0

14.2

1.5

65-Gal. / Com.

10.5

27.2

5.0

80-Gal. / Res.

13.5

14.2

1.5

80-Gal. / Com.

13.2

27.2

5.0

120-Gal. / Res.

20.8

14.2

1.5

120-Gal. / Com.

20.6

27.2

5.0