X-BAC BACnet Interface Module Installation and Configuration Manual

3

HT#

059294-00

B

OvervIeW

The BACnet Interface Module adds BACnet MS/TP communication capability to the M4-LHS control. It does that by connecting

to both, the control and the BACnet MS/TP network. All the BACnet settings are configured through the control. The BACnet

Interface Module has LEDs that can help in displaying communication status.

BACnet Interface Module

MSTP

1

2

3

A GND B

PRODUCT

COMM

RS485

X-BAC

RS485

to EMS

RJ45

Communication

to Control

Operation

LEDs

RJ11

to Extension

Mounting

Tab

ITeM LIST

• X-BAC BACnet Interface Module,

• RJ45 cables (Ethernet Cable),

InSTALLATIOn

The BACnet Interface Module communicates with the M4-LHS control using the RJ45 cable. Thus, it needs to be installed in close

proximity to the control.

• Mount the BACnet Interface Module on a flat surface next to the control.

• The module can be mounted horizontally or vertically.

• Keep the module away from extreme heat, cold, or humidity.

• Screw the module to the flat surface using the two side tabs with holes.

• No need to remove the BACnet Interface Module cover.

WIrIng

• No power wiring is required for the BACnet Interface Module. It gets its power through the control's

RJ45 connection.

• The module's MS/TP terminals are of the removal type. That facilitates easy wiring. Just unscrew the

terminal block side screws to remove the full terminal block.

BACnet Interface Module

MSTP

1

2

3

A GND B

PRODUCT

COMM

RS485

X-BAC

A (+)

Ground

B (-)

To BACnet

MSTP

BACneT MS/TP WIrIng

• Use 18# AWG Twisted Pair cable. The cable length must not exceed 3500 feet.

• Connect the MS/TP cable coming from the BACnet MS/TP network to the MS/TP terminals on the

BACnet Interface Module. Communication on the BACnet MS/TP network is polarity sensitive.

• The ground terminal (GND) MUST be connected to the BMS Ground.