Bacnet startup menu setup, Bacnet mode, Bacnet baud rate – LAARS X-BAC BACnet Interface Module - Install and Operating Manual User Manual

Page 5: Ms/tp address, Bacnet id, X-bac, Bacnet interface module

Advertising
background image

X-BAC BACnet Interface Module Installation and Configuration Manual

5

HT#

059294-00

B

BACneT STArTuP Menu SeTuP

-------- SETTINGS ----

Season

Winter

System Target 140

o

F

<System Settings>

<Maintenance>

<System Startup>

BACK ▲ ▼ SELECT

-- ARE YOU SURE? --

No

Yes

BACK ▲ ▼ SAVE

--- BACNET MODE ---

Disable

Enable

BACK ▲ ▼ SAVE

- BACNET BAUDRATE -

9600

19200

38400

BACK ▲ ▼ SAVE

----MS/TP ADDRESS----

1

[ ]

BACK ▲ ▼ SAVE

---- BACNET ID ----

477000

[

]

BACK ▲ ▼ SAVE

BACneT MODe

Enable, Disable

Default: Disable

Button: MENU/<System Startup>/.... Sensor Fault/BACnet Mode

• This menu option enables or disables the BACnet MSTP capability. When enabled,

additional BACnet settings shall be available for further customizing.

--- BACNET MODE ---

Disable

Enable

BACK ▲ ▼ SAVE

BACneT BAuD rATe

9600, 19200, 38400

Default: 19200

Button: MENU/<System Startup>/.... Sensor Fault/BACnet Mode/BACnet Baudrate

• For the control to communicate over a BAcnet MS/TP network, it must use the same Baud

rate as the rest of the network. The control offers three Baud Rates.

• If communication was not successful, the baud rate could be the cause. Check with the

network administrator for the network baud rate. Then match it on the control.

- BACNET BAUDRATE -

9600

19200

38400

BACK ▲ ▼ SAVE

MS/TP ADDreSS

1 to 127

Default: 64

Button: MENU/<System Startup>/.... /BACnet Mode/BACnet Baudrate/ MSTP Address

• Each device on the MS/TP network must have a unique address.

• This is the MS/TP address on a RS485 network. Its MS/TP range is 1 though 127.

• The MS/TP address must be provided by the Network Administrator.

----MS/TP ADDRESS----

1

[ ]

BACK ▲ ▼ SAVE

BACneT ID

1 to 4,000,000

Default:

Button: MENU/<System Startup>/.... / MSTP Address / BACnet ID

• The BACnet ID is a unique 32 bit number that identifies the control within the BACnet

network. No two ID shall be the same even if dealing across networks.

• It must be provided by the BACnet Network Administrator.

---- BACNET ID ----

[

]

BACK ▲ ▼ SAVE

LeD

Yellow LED

Flashes on communication between the BACnet Interface Module and the

control.

Green LED

Flashes on communication between the BACnet Interface Module and the

BACnet network.

Red LED

Flashes steadily to indicate the BACnet Interface Module is operational.

BACnet Interface Module

MSTP

1

2

3

A GND B

PRODUCT

COMM

RS485

X-BAC