When sensor plough,LED glittering and show “E1”

,Alarm with buzzer.; 

When sensor short curcuit, LED glittering and show “E2”

,Alarm with buzzer. 

Exceed temperature range alarm

: 

When sensor temperature more than+99℃ or less than -50℃

,Will show“HH”or“LL”。 

Press "Mute" more than 2seconds,Temperature control system close. 

 

4  Defrosting and Maintenance 

4.1  Defrosting 

There will be some frost build up on the surfaces of chamber after a long time running which

 

 

 

 

 

 

 

 

 

   

 

   

 

 

 

 

may decrease the performance of freezer. If the thickness of frost is more than 10mm thick,

 

 

 

   

   

 

   

   

 

 

 

 

defrosting operations are recommended. 

4.2  Maintenance  

External Casing: The cabinet is finished with painted epoxy. To maintain appearance the unit

 

 

 

   

 

 

 

 

 

 

 

 

 

should be wiped over with a non abrasive household cleanser and cloth. 

 

Internal Chamber: The chamber and door liner are manufactured from formed plastic. These

 

 

 

 

 

 

 

 

 

 

 

 

 

surfaces may be cleaned with a gentle household cleanser and cloth or sponge.  

 

The shelves are manufactures from plastic coated steel and a non abrasive cleanser should

 

 

 

 

 

 

 

 

   

 

 

 

 

be used.  

 

The magnetic door gasket should be cleaned with a mild detergent ensuring it is dried

 

 

 

 

 

 

 

   

 

 

     

 

completely after washing. If there are stains on the gasket, these can be spot cleaned with a

 

 

   

 

 

 

 

 

 

 

 

 

 

 

   

household cream cleanser.  Wipe away any residue/cleanser. 

 

Unit should be cleaned and ventilation outlets and compressor intakes checked for any

 

 

 

 

 

 

 

 

 

 

 

 

 

obstructions on a regular basis. 

 

4.3  Six Monthly Checks 

 

Refrigeration System Checks: 

 

Defrost unit and clean internal surfaces. 

Remove roughing filter from in front of condenser unit. Clean in warm soapy water. Allow filter

 

 

 

   

   

 

 

   

 

 

 

 

 

to dry naturally.  When dry re-install. 

Carefully vacuum dust from condenser. 

Check operation of condenser fan. 

Check compressor unit/s for excessive noise and or vibration. 

Electrical Maintenance (by qualified Electrician): 

 

All electrical terminations/connections should be checked for tightness. 

Motor currents should measured and documented. 

If a fan motor is fitted the fan motor is pre-lubricated with sealed bearings which should not

   

 

   

 

 

 

   

 

 

 

 

 

 

 

require maintenance for some time depending upon extent of usage. 

 