2000 Fire Door-Fan Manual

updated 2002-05-28

Page 9 of 58

OR

, Model E analog gauge clip

for models E43, E53, E54

The Gauge Clip attaches to the door

or the Aluminium frame.

1.

Loosen knob on gauge plate to
accommodate door thickness.

2.

Hold gauges at eye level.

3.

Rotate clamp to grip door.

4.

Tighten knob.

Gauges mounted on door.

Top 60-gauge slides up and
off to be used as handheld

as needed.

Zero gauges by blowing in the tubes and capping them

off with your thumb so the gauge stays at the top of its
range for 30 seconds. If the gauge falls while capping

the tube, there is a leak, stop to locate and fix it. Let
the gauge fall back down and zero with small
screwdriver supplied. Do not turn more than 3 turns!

After another 30 seconds of gently tapping the gauge
front, adjust the zero screw at the bottom of each

gauge until it reads zero with the small slotted blade
screwdriver. Tap the gauge with your finger to

remove the mechanism's friction (hysteresis), and re-
zero if necessary.


Move rocker switch to the right then turn the

blower mounted speed control.