Troubleshooting – Leslie Controls NYC Heat Exchanger User Manual

Page 17

Advertising
background image

Page 17 of 25


Valve Listing and Functions (refer to assembly drawing for particular size heater)
Item No.

ON

OFF

15

Flow diverter, primary flow to Pump 1, no flow to
pump 2

No flow to pump 1, flow to pump 2

16

Emergency pressure relief, flow to drain

No flow to drain

37

Hand Op Ball, re-circulation water to Cold inlet
water

No re-circulation water to Cold inlet
water

39

Gain Adjuster Valves

Adjust cold water flow to insure constant
temperature over the range of flow.

41

Hand Op. Ball, Supply cold water to blend valve

Shut off cold water to blend valve

42

Blend Valve, 150 F, Blending Water

No blending of water

43

Blend Valve, 130 F, Blending Water

No blending of water

46

Check Valve, no back flow of hot water from heat
exchanger

N/A

47

Solenoid Valve, Hot water to second blend valve

No hot water to second blend valve

59

Gate valve, Supply steam

Shut off steam supply

68

Hand Op Ball, Bypass condensate cooler

Flow through condensate cooler

76

Gate valve, flow of condensate to drain

No flow of condensate to drain

78

Needle valve, Steam to gauge and pressure sensor

Shut of steam for maintenance of gauge

101

Condensate Diverter, Condensate through Cooler

Condensate

to

drain

and

bypass

Condensate Cooler in fail mode.




TROUBLESHOOTING

Condition

Possible Cause

Fix

No Steam/Low Steam

Adjust steam regulator.

Blocked tubes in heat exchanger

Flush Heat exchanger.

Drain valves from steam traps are shut

Open drain valves.

Condensate drain line is blocked or valves are turned off

Clear line and turn on valves.

Solenoid is tripped

Turn on Manual switches “H-1” and
H-2”

Blend valve element defective

Test blend valve element and replace if
necessary.





No Hot water

Over temperature condition was reached and Thermo Switches
are still engaged.

Find out why over temperature
happened and let Thermo Switches
reset.

Shut of the Gain adjusters

Cold water main from street is shut off.
Reset Gain Valves (39)

Steam pressure above 15 psi

Steam adjust steam pressure or fix
steam regulator.

Steam Traps broken and steam is being sent to the condensate
cooler

Fix Steam traps.




System
Tripped

Blend valve element defective.

Test blend valve element and replace if
necessary.