pump should fail then Red light for “NO_FLOW” will
light. Follow instructions for isolating this pump and
starting primary pump or shutting down system.




























F. OPERATION OF SWITCH

PANEL

(Ref Figure 2)

Light/Switch

Indication

Notes

Power On

Green

Electrical
power is
being
supplied to
unit.

Pump 1 On

Primary pump P1 is
on. Green

Pump can
have power
but not pump
fluid

Pump 2 On

Secondary Pump
P2 is on. Green

Pump can
have power
but not pump
fluid

No Pump
Flow

Re-circulation
system flow has
stopped. Red

Water
pressure
before pumps
is same as

after pumps

No. 1 Heater
Over Temp

Hot water is off.
Red

One or more
temp
controllers on
side one
detected an
over temp
condition.

No. 2 Heater
Over Temp

Hot water is off.
Red

One or more
temp
controllers on
side two
detected an
over temp
condition.

H-1

Turn hot water to
side one on

Turns system
on (Both
switches need
to be on)

H-2

Turn hot water to
side two on

Turns system
on (Both
switches need
to be on)

P-1

Select primary
pump on, secondary
off

Power to
primary
pump. Off to
secondary

P-2

Select secondary
pump on, primary
off

Power to
secondary
pump. Off to
primary

Reset

Momentary switch
to reset from a fail
condition

Fail condition
latches unit to
supply only
cold water















G. OPERATION DUE TO OVER
TEMPERATURE CONDITIONS


Temperature switch settings:

First switch = 180 degrees F

WARNING!

Pressure may be present in the pump body. Loosening

flange bolts and shifting pump assembly slightly to

allow pressurized water to escape can relieve this

pressure. Failure to follow these instructions could

result in serious personal injury or death

WARNING!

When disassembling a gasketed joint, always use a new

gasket upon reassembly. NEVER RE-USE OLD

GASKETS. Failure to follow these instructions could

result in serious personal injury or death

WARNING!

Pressurize the body slowly while checking for leaks at

all joint with gaskets. NEVER RE-USE OLD

GASKETS. Failure to follow these instructions could

result in serious personal injury or death

CAUTION!

Do not run pumps dry, seal damage may occur. Failure

to follow these instructions could result in serious

personal injury or death

CAUTION!

IF AN OVER TEMPERATURE CONDITION WAS
DETECTED:

1.

The hot water supply is shut off and only cold
water is supplied to building.

2.

Re-circulation pump power is turned off.

3.

Condensate bypasses cooler.

RESET WILL OCCUR AUTOMATICALY AFTER
WATER TEMPERATURE REDUCES AND
RECIRCULATION CONTINUES