Connecting to the communications port, Connecting the remote emergency power off – Compaq Presario 3000 Series User Manual

Page 27

Advertising
background image

Installation 2-5

Connecting to the Communications Port

The 3000 Series UPS models include a communications port for data
exchange with the host computer.

IMPORTANT: Compaq Power Management Software, LanSafe III, and FailSafe III require
the communications port to be appropriately cabled to the host computer.

Connect the UPS/computer interface cable (supplied) from the
communications port on the UPS to the appropriate communications port on
the host computer.

CAUTION: To avoid damaging the equipment,

do not use the communications

cables (part numbers 142260-001 and 142260-002) supplied with earlier UPS
models. The UPS/computer interface cable is required to carry power and is
wired differently than earlier communications cables.

REMO

TE

PO

WER OFF

Figure 2-1. Connecting the UPS/computer interface cable

Connecting the Remote Emergency Power Off

The 3000 Series UPS models include a Remote Emergency Power Off
(REPO) port. When properly wired, the REPO port allows the power to the
UPS output receptacles to be switched off from a remote location.