background image

4-10 Compaq 3000 Series UPS Operation and Reference Guide

Table 4-2

Operating Ranges (VAC) – North America and Japanese Models

Nominal Level

Normal Range

Extended Range

100

80 to 120

Not applicable for R3000j

110

88 to 132

72 to 132

120

96 to 144

78 to 144

127

102 to 152

83 to 155

Table 4-3

Operating Ranges (VAC) – All High Voltage Models

Nominal Level

Normal Range

Extended Range

208

166 to 250

Not applicable for

R3000h-NA

220

176 to 264

143 to 264

230

184 to 276

150 to 276

240

192 to 288

156 to 288

3.

For nominal voltage level setting, select configuration parameters
1, 2, 3, or 10 (see Table 4-1).

4.

Access parameter 4 to switch from normal to extended range (see
Table 4-1).