61

Battery Size Requirements and Maintenance

These panels require a 24 volt gel-cell battery for proper operation. 24 hours of standby power is required for

Local Systems and Central Station (NFPA-72).
The chart below will assist you in selecting the proper size battery: (Does not include LED Annunciator)

Number

of Smoke

Detectors

Number of

Bells

(100mA each)

Auxiliary Power

Requirements

Standby Hours

Required

Battery Size

(2 Required)

Part/Stock

Number

0-100

0-10

0-25mA

24

24AH

BT-80/5130084

0-100

0-10

0mA

90

90AH

BT-120/5130090

0-100

0-10

0-30mA

90

18AH

BT-180/5130086

Note: Maximum allowed battery size for UL Listings is 12AH. FM and others may require more than 24 hours

of standby time and may use larger batteries. Batteries rated above 12AH require a separate battery cabinet (Pot-

ter Model BC-2). Mark the purchase date on the batteries. Test the batteries at least semi annually according to

the battery test methods in NFPA72 or the battery manufacturers instructions. Replace the batteries if they either

fail the test or after four years of use.