Ps10 series, Pressure switch, Local bell for waterflow connection fig. 6 – Potter Releasing Systems User Manual

Page 78

Advertising
background image

78

MFG. #5400928 - REV D

1/08

PRINTED IN USA

PAGE 2 OF 3

PS10 SERIES

PRESSURE SWITCH

Typical Sprinkler Applications

Switch Clamping Plate Terminal

Dimensions

OUTGOING

INCOM

ING

DWG# 923-3

Low Pressure Signal Connection

Waterflow Signal Connection

WET SYSTEM WITH

EXCESS PRESSURE

WATER

MOTOR

GONG

PS10

RBVS

WET

SYSTEM

ALARM

CHECK

VALVE

OS & Y

VALVE

WATER

BY-PASS

VALVE

WET SYSTEM WITHOUT

EXCESS PRESSURE

WATER

MOTOR

GONG

WET

SYSTEM

ALARM

CHECK

VALVE

OS & Y

VALVE

RBVS

WATER

BY-PASS

VALVE

RETARD

PS10

DRY

SYSTEM

ALARM

CHECK

VALVE

OS & Y

VALVE

WATER

BY-PASS

VALVE

CHECK

VALVE

RBVS

DRY SYSTEM

PS10

WATER

MOTOR

GONG

DWG. #923-2AA

Fig. 2

Fig. 4

Fig. 5

Fig. 3

Fig. 1

An uninsulated section of a single conductor

should not be looped around the terminal and

serve as two separate connections. The wire

must be severed, thereby providing supervision

of the connection in the event that the wire

becomes dislodged from under the terminal.

Closing of any shutoff valves between the alarm check valve and the PS10 will render the PS10

inoperative. To comply with NFPA-72 any such valve shall be electrically supervised with a

supervisory switch such as Potter Model RBVS.

Local Bell For Waterflow Connection

Fig. 6

NOTE: To prevent leakage, apply Teflon tape sealant to male threads only.

2.87

[72.97]

4.22

[107.19]

2.48

[62.87]

3.78

[95.89]

3.20

[81.28]

1.60

[40.64]

GROUND

SCREWS

DWG# 930-1

1/2" NPT

ADJUSTMENT

KNOB

EOLR

TO FIRE ALARM PANEL

DWG# 928-1

EOLR

TO FIRE ALARM PANEL

DWG# 928-2

POSITIVE DC

OR HOT AC

BELL

NEGATIVE DC

OR NEUTRAL AC

LINE

LOAD

DWG# 928-3