Pfc-4410rc, Releasing control panel – Potter Releasing Systems User Manual

Page 64

Advertising
background image

64

PRINTED IN USA

PAGE 1 OF 2

MFG #5401250 - REV A

12/09

PFC-4410RC

RELEASING CONTROL PANEL

Potter Electric Signal Co., LLC • St. Louis, MO • Cust Service: 866-240-1870 • Tech Support:866-956-1211• Canada 888-882-1833 • www.pottersignal.com

• Multi-Hazard Operation

• Four Class B Initiating Circuits

• Two Class B Supervisory Circuits **

• Four Class B Output Circuits

• Programmable Cross Zoning

• Supervised Microprocessor

• 32 Character Alpha-Numeric LCD Display

• Custom Banner Message and Zone Description text

• Custom Zone Description Text

• On Board Menu Driven Programming Controls

• Releasing Circuits Protected From False Activation

• Continuous or Timed Discharge

• 40 Event History Buffer

• Walktest with Automatic Time-out

• Alarm, Trouble Supervisory, and Waterflow relays

• Optional Class A Initiating Zone and output module

• 34 character LED supplemental display

• 19 Standard Programs in Panel Memory

• Password Protection for all Programming

• 24 Hour Clock

• Suitable for agent or water-based extinguishing

• Programmable pre-discharge timers*

• One Class B Abort circuit* (Defaults to additional supervisory zone

in water based mode.)

• Three Abort modes*
* Available in Chemical mode only

** One zone programmable as abort in chemical mode.

Ordering Information
Model Number

Description

Stock Number

PFC-4410RC

4 Zone Releasing Control (White Cabinet)

3006144

PFC-4410RC

4 Zone Releasing Control (Red Cabinet)

3006142

PFC-TW

Bezel for Semi-Flush Mounting (White)

5090157

PFC-TR

Bezel for Semi-Flush Mounting (Red)

5090155

BT-40

Battery, 12V 4AH for 24 hour standby (2 Req’d)

5130092

BT-80

Battery, 12V 8AH for 60 hour standby (2 Req’d)

5130084

BT-120

Battery, 12V 12AH for 90 hour standby (2 Req’d)

5130090

BT-180

Battery, 12V, 18AH for 90 hour standby (2 Req'd)

5130086

CA2Z

2 Zone Class A Initiating Circuit Module

3006013

CAM

Class A Indicating Circuit Module

3005300

ARM-44

Relay Module for PFC-4410RC

3006221

ARM-2

Auxiliary Relay Module

3004725

RA-4410RC

Remote Annunciator

3006400

BB-RA-44R

Surface Mount Back Box for RA-4410RC (Red)

3006401

Dimensions: 18 ¼" x 14 ½" x 4 ¾"

General Description

The Potter Model PFC-4410RC is a flexible multi-hazard releasing control

panel that is well suited for a number of applications. The PFC-4410RC is

listed for use with pre-action and deluge sprinkler suppression systems and

agent based fire suppression systems.

The panel utilizes a microprocessor-based system that has 19 Standard

Programs, which covers a majority of installations. The simple to follow Menu

Structure programs the entire system in a matter of minutes. In addition to the

Standard Programs, the panel allows custom programming to accommodate

any installation.

The panel is Ninth Edition UL listed, ULC listed, Factory Mutual, California

State Fire Marshal (CSFM) and New York Materials Equipment Acceptance

(MEA) approved.

The PFC-4410RC is housed in a durable steel cabinet with removable door

and key lock. The panel is available in either a red or white finish and an

optional flush mount trim ring is available. The cabinet contains knockouts

on the side, back and top of the cabinet to ease installation. In addition, the

cabinet will house up to 18 amp-hour batteries that will provide in excess of

90 hours of standby power.

UL and ULC Listed, FM Approved, NYMEA Accepted, and CSFM

Approved

Advertising