4.1

REMOTE OPTIONS

Remote Options

This section allows the information needed for Remote Command/Remote Programming

operation to be entered. A description of the Remote Options follow.
Note: A complete functional checkout of the panel is required following any programming or

reprogramming.

4.2

RMT KEY:

Remote Key

This option allows you to enter a code of up to eight digits for use in verifying an alarm or

service receiver authority to perform a remote command/programming session. The receiver

must give the correct key to the panel before being allowed access. Default is blank.
To enter a new Remote Key, press a top row Select key and enter any combination of up to

eight digits. The numbers you enter appear as asterisks. Press COMMAND.

4.3

MFG AUTh NO YES

Manufacturer Authorization

Enter YES to allow service technicians to access the panel when required during system service

or troubleshooting. This automatically expires within one hour.
Remote service is provided on a read only basis: technicians can look at the system

programming and make suggestions only.

4.4

ARMED RINGS:

0

Armed Rings

Enter the number of rings the panel counts within a two minute period before answering the

phone line. Enter any number from 1 to 15. Default is 0 rings.
If 0 (zero) is entered, the panel does not answer the phone. If NONE is selected as the

Communication type, the ring detect function is disabled and the 984 Command function must

be used to seize the phone line. See Manual Telephone Line Seizure Section in the Appendix.
Answering machine bypass procedure: Entering a number greater than 0 (zero) into Armed

Rings allows a central station operator to connect remotely with the panel.
How it works: The operator calls the panel, rings the phone once and then hangs up. The panel

stores this attempt to communicate. The operator then calls back within 30 seconds causing the

panel to seize the phone line and allow remote programming.

4.5

ALR RCVR NO YES

Alarm Receiver Authorization

Enter YES to enable the panel to accept remote commands and programming from the alarm

receiver. The Remote Key option can also be required.
When YES is selected, the panel requests the alarm receiver key during its first alarm

communication with the first receiver. The panel retains this alarm receiver key in memory

and allows remote commands to be accepted from the alarm receiver. If an alarm occurs during

a remote connect, the alarm report is immediately sent to this receiver only.
Enter NO to not accept remote commands and programming from the alarm receiver.

4.6

SVC RCVR NO YES

Service Receiver Authorization

YES enables the panel to accept remote commands and programming from a secondary service

receiver other than the alarm receiver. A Remote Key can also be required.
With YES selected, the panel requests the service receiver key the first time it is contacted by

the service receiver. The panel retains this service receiver key in memory and accepts remote

commands from the service receiver.
If an alarm occurs during a remote connect, the panel disconnects from the service receiver

and calls the alarm receiver. Alarm reports are only sent to the alarm receiver. It is important

that the alarm receiver key and the service receiver key programmed at the central station are

NOT the same so the panel can determine the difference between receivers.
When NO is selected, the panel does not accept remote commands and programming from a

secondary service receiver.