This section allows you to select system wide parameters used in the operation of the PFC-

7500/PFC-7501 system.

5.2

CRS ZONE TM:

0

Cross Zone Fault Time

Enter the time allowed after a zone trips to indicate a zone fault condition. When a zone

programmed for cross zoning trips, the panel begins counting down the Cross Zone Fault Time

you enter here. If the same zone or another zone trips within this time, or prior to a Sensor

Reset, an alarm report is sent to the receiver for both zones.
If the Cross Zone Fault Time expires without the second zone trip, a zone fault report from the

first zone is sent to the receiver.
The Cross Zone Fault Time can be set from 4 to 250 seconds in one second increments. Enter 0

(zero) to disable the Cross Zone Fault Time feature.

5.3

RETARD DLY:

0

Zone Retard Delay

Enter the time allowed for zones to be shorted before the panel acknowledges the short as an

alarm. This option is primarily used on waterflow zones where fluctuations in the flowswitch

may short the zone in the absence of an actual alarm condition.
The Retard Delay can be set from 0 to 250 seconds in one-second increments.

5.4

PWR FAIL hRS:

1

Power Fail Delay

This option tracks the duration of an AC power failure. When the AC power is off for the length

of the programmed delay time, an AC power failure report is sent to the receiver.
The delay time can be set from 0 to 15 hours. Default is 1.

5.5

RST SBYP NO YES

Reset Swinger Bypass

When YES is selected, a swinger bypassed zone is automatically reset if it remains in a normal

condition for one hour after being bypassed. A report of the reset is automatically sent to the receiver.