Potter RA-7692 User Manual

Page 15

Advertising
background image

Annunciator Manual • 8910224 • Rev C • 6/09

15

CODE

To change the system user code, press CODE, enter the current user

code followed by 0 + 1, and then enter the new 4-digit user code.
The user code must always be 4 digits.

SPECIAL

Pressing the SPECIAL key and entering the user code initiates the

Fire Drill function.
The Fire Drill sounds the alarm bells and annunciator sounder for

the duration of the Bell Cutoff time. If the Bell Cutoff time is set

to zero (0), the Fire Drill continues until the bells are silenced by

entering a code. No annunciator LEDs are turned on and no reports

are sent to the central station during the Fire Drill.
In the event of a real fire during a fire drill, the system sends a

report to the central station and the LED for any fire-detecting zone

glows red on the RA-7692.

Manual Fire Alarm

To manually initiate a Fire Alarm, press and hold the TEST and CODE

keys simultaneously for about 2 seconds until the alarm sounds.

Resetting Sensors

Use this function to reset smoke detectors after an alarm when the

Fire zone light is flashing in alarm memory.
Enter COMMAND + 4 + 7 to perform a Sensor Reset. The system

resets the smoke detectors and stops the flashing light if the zone

restores to normal.

You can also initiate a Sensor Reset by pressing the RESET

function key followed by your User Code.

Testing the System

It is good practice to test your system at least once each week. This

assures you that the system is working correctly and identifies any

potential problems.
Enter COMMAND + 4 + 1 to perform a system test. The bell rings

for 2 seconds then the battery and communications to the central

station are tested.
You can also initiate a System Test by pressing the TEST function

key followed by your User Code.

User Codes

Use this function to change the current User Code.
Press the CODE key followed by the current User Code. You will

hear one beep if successful. Enter 0 (zero) + 1. Enter the new

4-digit User Code.

2-Button Fire Keys

If your system has a label showing a Flame under the TEST and

CODE keys, the optional Panic key function has been enabled.
Press the two keys over the icon, and hold them down for at least

2 seconds. The system will send a Fire report to the central station.

The annunciator beeps to confirm the Fire key entry.