Crestron DIN-8SW8

DIN Rail High-Voltage Switch

Setup

Network Wiring

When wiring the Cresnet network, consider the following:

• Use Crestron Certified Wire.

NOTE: Cresnet HP cannot be used.

• Use Crestron power supplies for Crestron equipment.
• Provide sufficient power to the system.

CAUTION: Insufficient power can lead to unpredictable results
or damage to the equipment. Please use the Crestron Power
Calculator to help calculate how much power is needed for the
system (

www.crestron.com/calculators

).

• Use of a Cresnet hub/repeater (DIN-HUB) is advised whenever the

number of Cresnet devices on a network exceeds 20 or when the
combined total length of Cresnet cable exceeds 914 meters (3000
feet).

For more details, refer to “Check Network Wiring” which starts on page
23.

Identity Code

The Net ID of the DIN-8SW8 has been factory set to 89. The Net IDs of
multiple DIN-8SW8 devices in the same system must be unique. Net IDs
are changed from a personal computer (PC) via Crestron Toolbox™
(refer to “Establishing Communication” on page 18).
To set the Net ID using the front panel:

1. Press the SETUP button to enter the Setup mode. The SETUP

LED illuminates.

2. Press the left button under the NET ID display to change the most

significant digit of the Net ID or press the right button under the
NET ID display to change the least significant digit of the Net ID
number.

Operations & Installation Guide – DOC. 6666B DIN Rail High-Voltage Switch: DIN-8SW8