Operation – Crestron electronic GreenLight DIN-8SW8 User Manual

Page 24

Advertising
background image

DIN Rail High-Voltage Switch

Crestron DIN-8SW8

Operation

Net ID

Use the NET ID buttons to change the Net ID of the DIN-8SW8. For
information on Net ID, refer to “Identity Code” which starts on page 9.

Manual
Control

The state of each output can be manually controlled from the front
panel.
To toggle the output between off and on, tap the appropriate button
(1 – 8). The corresponding LED illuminates and the output state is
shown on the NET ID display (“oF” for off, “On” for on) for two
seconds after the button is released.

NOTE: The control system program may change the settings if the
Override mode is not enabled.

Override
Mode

The Override mode overrides the control system program and sets all of

the output states to the stored override values. For instructions on saving
override settings, refer to “Save Override Settings” on page 21.

To enable Override mode, press and release the OVR button. The OVR

LED flashes slowly.

NOTE: If the Override mode was enabled from an external device (i.e.,
a contact closure is present on the OVERRIDE terminals), the OVR
LED will flash quickly. Pressing the OVR button has no effect.

To disable Override mode, press the OVR button again. The OVR LED

extinguishes and the outputs return to the states set by the control system
program.

NOTE: If override states have not been stored, the factory default
override state is all loads on.











20

DIN Rail High-Voltage Switch: DIN-8SW8 Operations & Installation Guide – DOC. 6666B