Odgsr series outdoor gas fireplace, Clearance to combustibles, Mantels – Vermont Casting ODGSR42A User Manual

Page 5: Hearth, Screened porch installation

Advertising
background image

5

ODGSR Series Outdoor Gas Fireplace

20007114

Clearance to Combustibles

Appliances

Top ..........................................................0” (0 mm)

Bottom .....................................................0” (0 mm)

Side .........................................................0” (0 mm)

Back ........................................................0” (0 mm)

Perpendicular Sidewall ...........................0” (0 mm)

Top of unit to ceiling ..........................36” (914 mm)

Front of unit to combustibles .............36” (914 mm)

Mantels

\

WARNING: A 4" hood must be used if a
mantel is to be installed.

The height that a combustible mantel is fitted above the
fireplace is dependent on the depth of the mantel. This
also applies to the distance between the mantel leg (if
fitted) and the fireplace.
For the correct mounting height and widths refer to
Figures 3a and 3b
Noncombustible mantels and legs may be installed at
any height and width around the appliance.

J

F

G

H

I

Mantel

Leg

CFM164a

Mantel Leg Chart

06/22/01 sta

CFM170

DV Builder Front

View

O

N

M

L

K

Ref.

Mantel

Ref.

Mantel Leg From

Leg Depth

of Comb. Opening

F

14" (356mm)

K

14" (356mm)

G

12" (305mm)

L

12" (305mm)

H

10" (254mm)

M

10" (254mm)

I

8" (203mm)

N

8" (203mm)

J

1¹⁄₂" (38mm)

O

1¹⁄₂" (38mm)

Black Sur-

round Face

CFM164

CFM170

Fig. 3b Combustible mantel leg minimum installation.

Side of

Combustion Chamber

Hearth

A hearth is not mandatory but is recommended for
aesthetic purposes. We recommend a noncombustible
hearth.

Ref.

Mantel

Ref.

Mantel From Top

Shelf Depth

of Comb. Chamber

Y

8" (203mm)

A

28" (711mm)

Z

1¹⁄₂" (38mm)

B

26" (660mm)

CFM146

A B

Y

Z

Fireplace

CFM146

DV Mantel Chart

7/5/01 sta

Top of Combustion

Chamber

Fig. 3a Mantel clearances.

Side View

When using paint or lacquer to finish the
mantel, such paint or lacquer must be heat
resistant to prevent discoloration.

Screened Porch Installation

The ODGSR may be installed safely and is design
certified by CSA to be installed in a screened porch with
these guidelines:

Minimum porch area ...............................96 sq. feet (9sq m)
Minimum celing height ................................. 92" (2,337 mm)
Minimum of two (2) walls must be screened
Minimum top of screen height, side walls ....6'6" (1,981 mm)
Minimum screen area .............................64 sq. feet (6sq m)

Advertising
This manual is related to the following products: