Odgsr series outdoor gas fireplace, Gas line installation – Vermont Casting ODGSR42A User Manual

Page 7

Advertising
background image

7

ODGSR Series Outdoor Gas Fireplace

20007114

FP1414

ODUVSR

valve access

11/24/03 djt

FP1414

Fig. 5 Valve access.

FP1415

lift brick access

11/24/03 djt

Majestic Logo

Brick

Fig. 6 Lift brick with logo on it to access valve.

FP1415

FP1416

ODUVSR

part id

11/24/03 djt

Nailing

Flange

Valve Access Panel

Firebox

Grate

Screen

Standoff

Surround

Gas

Line Ac-

cess

FP1416

Fig. 7 Parts identification.

*Do not install

header until unit

is in place.

Gas Line Installation

This appliance must be isolated from the gas supply
piping system by closing its individual manual shut off
valve during any pressure equal to or less than 1/2 psig
(3.45 kPa).

The appliance and its individual shutoff valve must be
disconnected from the gas supply piping system during
any pressure testing of that system at test pressures in
excess of 1/2 psig (3.45 kPa).
If gas piping from the source to the appliance location
has not been accomplished, install the required pipe.
Consult local plumbing code to assure proper pipe size.
The gas pipeline can be brought in through the right
side of the appliance. A knockout is provided to allow
for the gas pipe installation and testing of any gas con-
nection.
NOTE: The gas line connection can be made

wit

h 3/8"

copper tubing approved for propane or natural gas, 1/2"
rigid pipe or an approved flex connector, then reduced
to 3/8" to the appliance. Because some municipalities
have some additional local codes, it is always best to
consult your local authority.
U.S.: Consult the current National Fuel Gas Code, ANSI
Z223.1/NFPA 54.
Canada: CSA - B149.1 installation code.
Test for leaks. Use a 50/50 solution of liquid soap and
water to test for leaks at gas fittings and joints. Apply
water/soap solution with brush only - do not over apply.
NEVER
test with an open flame.
The gas control is equipped with a captured screw type
pressure test point, therefore it is not necessary to pro-
vide a 1/8" test point up stream of the control.
When using copper or flex connector use only approved
fittings. Always provide a union so that gas line can
be easily disconnected for burner or fan servicing.
See gas specification for pressure details and ratings.
NOTE: If flex connector is used, it must be kept inside
of the appliance. (Fig. 8)

FP598

Fig. 8 Typical gas supply installation.

1/2" Gas Supply

1/2" x 3/8" Shut-off Valve

3/8" Union

3/8" Nipple

3/8"

Nipple

GF598

nvb GAS SUPPLY INSTALL

12/4/97

Advertising
This manual is related to the following products: