3.1 Uncrating and Inspecting

Check for any damage that may have been incurred during shipment. If damage is

found, document the damage with the carrier and immediately contact an authorized

Reznor

®

distributor.

Check the gas specifications and electrical voltage (system rating plate is in the control

compartment) to be sure that they agree with the utilities at the installation site.
Locate the 4x4 junction box with a 3-positon switch shipped inside the unit. (

NOTE:

Two exceptions - 1) If an optional remote console was ordered, this switch is mounted

on the console which is shipped separately. 2) If gas control Option AG37 was ordered,

the junction box is not included)

3.0 Uncrating and

Preparation

4.0. Clearances

and

Dimensions

4.1 Clearances to Combustibles

Clearance to combustibles is defined as the minimum distance from the heater to a

surface or object that is necessary to ensure that a surface temperature of 90°F above

the surrounding ambient temperature is not exceeded.

Top

Control Side*

Opposite Side

Bottom

0

0

0

0

*In order to service the system, the minimum clearance on the control side of the unit

must be equal to the width of the unit.

3.2 Preparing for

Installation

Shipped-Separate Components

Depending on the gas and/or air controls selected, the following additional parts are

shipped loose in the unit or shipped separately.

Gas Control Options

Shipped-Loose Parts

AG30, AG32, AG33, AG35

*Temperature Selector , Discharge Air Sensor

AG31

*Temperature Selector, Discharge Air Sensor, Space

Override Thermostat

AG36

Remote Console

AG49, AG50

Control Switch, P/N 29054

*If an optional remote console is ordered, this control may have been ordered to be

mounted on the console. The console is shipped separately.

Be sure that all shipped-separate accessories for the installation are available. Shipped-

separate accessories could include a roof curb, an indoor filter cabinet, an outside air

hood, a disconnect switch, a supply gas regulator, a door switch, an evaporative cool-

ing module, a fill and drain or freeze kit, and/or a water hammer arrestor.
Be sure that all necessary equipment, tools, and manpower are available at the instal-

lation site.

4.2 Dimensions

4.2.1 Dimensions of Models ADF/ADFH Sizes 300 and 500

Dimensions (inches) - Illustration in FIGURE 1A (Sizes 300 and 500)

Models

Horizontal Discharge

Vertical** Discharge

ADF300

ADF500

ADF300

ADF500

ADFH300

ADFH500

A

34

47-3/4

34

47-3/4

34

47-3/4

B

31-1/16

44-13/16

31-1/16

44-13/16

31-1/16

44-13/16

C

85-13/16

85-13/16

85-13/16

85-13/16

109-1/2

109-1/2

D

11-27/32

12-11/16

-

-

-

-

E

15-5/16

17-11/16

-

-

-

-

F (inside)

15-15/16

14-13/16

15-15/16

14-13/16

15-15/16

14-13/16

G

17-1/2

16-3/8

-

-

-

-

H (inside)

13-3/4

16-1/8

-

-

-

-

J

-

-

64-19/32

62-11/32

64-19/32

62-11/32

K

-

-

13-13/16

16-1/16

13-13/16

16-1/16

M

-

-

7

8-1/8

7

8-1/8

N

-

-

8-1/8

21-3/4

8-1/8

21-3/4

P

-

-

7-13/32

7-13/32

31-3/32

31-3/32

** Models ADFH 300/500

have a motor compartment

required for high

temperature discharge.

Models 300/500 with

optional vertical discharge

have same cabinet length

as the standard horizontal

discharge unit.

Advertising
This manual is related to the following products: