Rogue Engineering 1950-250 User Manual

Page 10

Advertising
background image

Modbus/SDI-12 Gateway User Manual

Page 10 of 12

Last Updated: August 20, 2013

Command 1 Age Option

13109

1

Command 1 Future Expansion

13110

10

Command 2 Sequence

13120

20

Command 3 Sequence

13140

20

...

Command 100 Sequence

15080

20

Table A1 – Device Modbus Register

Item Detail

Item Name

Description

Configuration Name

80 char max, packed into 2 char per register

Last Modified

4 registers as 64bit long integer, Visual C# representation

Modbus Direction

0=Modbus DCS, 1=SDI-12 DCS (not supported yet)

Modbus Address

Modbus Baud Rate

one of 9600, 19200, 57600

SDI Power

1=Always Off, 2=Always On, 3=On when polling

Poll Interval

in seconds, only valid if using SDI Power option 3

Power Up Delay

in milliseconds

Number of Commands

1 to 100

Auto sequence Option (internal
use)

1=commands after the first one have their first register
set automatically

Command x Sensor Address

0-9 or a-z or A-Z

Command x Sensor Poll Interval

in seconds, valid if SDI power option is 1 or 2

Command x First Input or Holding
Register

first Modbus register where data will be available, see
Command Table for data lengths (actual register
(protocol address) is one less than this number)

Command x

see Command Table

Command x First Value

1 to 9

Command x # of Values

1 to 9

Command x CRC Option

1=use CRC, only valid with certain commands

Command x Data Format

0=16 bit integer, 1=32 bit integer, 2=32 bit float, 3=1
character per register, 4=2 characters per register packed

Command x Word Order

0=MSW first, 1=LSW word first, only valid for 32 bit
data formats

Command x Age Option

1=append aging information after data

Command x Future Expansion

N/A

Table A2 – Command Items Detail Description