Modbus/SDI-12 Gateway User Manual

Page 9 of 12

Last Updated: August 20, 2013

Appendices

This information is provided for advanced users only, and allows for configuration of units

without using the provided Windows software. Typical users do not need this information.

Appendix A - SDI-12 Configuration Register Map

The following register is valid for firmw3are version 5400-362-03 for the SDI-12/Modbus

Translator hardware. All configuration data is accessed via Modbus functions 3, 6, and 16 (holding
registers). The unit will respond to commands for any Modbus address for this range of registers.

Modbus Registers

Item Name

Register #

Length

Reserved

10000

3000

Configuration Name

13000

40

Last Modified

13040

4

Modbus Direction

13044

1

Modbus Address

13045

1

Modbus Baud Rate

13046

1

SDI Power

13047

1

Poll Interval

13048

1

Power Up Delay

13049

1

Number of Commands

13050

1

Auto sequence Option (internal use)

13051

1

Reserved

13052

8

Firmware Version Number

13060

1

Firmware Revision Number

13061

1

Reserved

13062

37

Configuration Set (internal use, write 1 to implement newly written
configuration)

13099

1

Command 1 Sensor Address

13100

1

Command 1 Sensor Poll Interval

13101

1

Command 1 First Input or Holding Register; actual register
(protocol address) is one less than this number

13102

1

Command 1

13103

1

Command 1 First Value

13104

1

Command 1 # of Values

13105

1

Command 1 CRC Option

13106

1

Command 1 Data Format

13107

1

Command 1 Word Order

13108

1