Rogue Engineering 1950-250 User Manual

Page 5

Advertising
background image

Modbus/SDI-12 Gateway User Manual

Page 5 of 12

Last Updated: August 20, 2013

Modbus Settings

Along the left side of the Configuration tab, you have the following options:

MB Address – This is the Modbus address to which the unit will respond when installed

in the field, after configuration.

Baud Rate – This is the baud rate to be used for the final field installation.

SDI-12 Power Control – This selects when power is applied to the +14V SDI Power

terminal. Use Always Off if the devices have another power source, Always On to
provide power continuously, or On When Polling to power the terminal only when
polling sensors.

Poll Interval – If SDI-12 Power Control is set to On When Polling, this sets the number

of seconds between consecutive attempts to poll all sensors.

Power up Delay – If SDI-12 Power Control is set to On When Polling; this sets the delay

in milliseconds between application of power and the first attempt to poll a sensor.

Sensor Commands

Use the following options to manipulate the list of sensor commands:

Add New Command to List – Click this button to add a command.

Remove Selected Command – Click to remove the currently highlighted command from

the list.

/\ and \/ buttons – Click to move the currently highlighted command up or down in the

list.

When you have added one or more commands to the list, click on a command to

highlight it and then set the options for that command below the list in the Command Detail
panel:

Address – Enter the one character SDI-12 address of the sensor, typically 0-9 or a-z or

A-Z

Command Drop-down Box (default of Measurement) – Select the SDI-12 command to

use.

CRC check-box – Most commands allow optional use of CRC validation. (CRC

validation is requested by default)

Poll Interval – If the SDI-12 Power Control is not set to On When Polling, this sets each

command's desired polling interval in seconds.

First Value – For commands that may return multiple values, enter the sequence of the

first value to be saved.

# Of Values – For commands that may return multiple values, enter the number of values

to be saved. For example, if First Value is 4, and # of values is 2, then the 4

th

and 5

th

values returned from this sensor command will be saved, and any others will be ignored.

Advertising