Encore 1450 non-catalytic woodburning stove, Alcove installations, Construction requirements – Vermont Casting 1450 User Manual

Page 13

Advertising
background image

13

Encore 1450 Non-Catalytic Woodburning Stove

30002425

ST253b

Encore

trim clearances

02/01 djt

C

C

A

B

D

Fireplace and Mantel Trim Clearances

Unprotected

Protected

A. Mantel

38” (965 mm)

22” (559 mm)

B. Top Trim

27” (686 mm)

20” (508 mm

C. Side Trim

10” (254 mm)

--

D. Side Wall

18” (457 mm)

8” (203 mm)

ST253b

Fig. 16 Maintain clearances to combustible components of
the mantelpiece.

Side

Wall

Alcove Installations

Because of their restricted air flow and heat reten-
tion characteristics, alcove installations have specific
construction requirements and special clearances. No
rear stove or chimney connector heat shields are used
in alcove installations. Bottom heat shield requirements
remain the same as for other installations.
ALCOVE INSTALLATION OF THE ENCORE IS NOT
PERMITTED IN CANADA.

Construction Requirements

The following illustrations show noncombustible ceiling
framing and maximum and minimum permitted dimen-
sions for alcove construction.

36"

Max.

48" Min.

ST502

Intrepid

Alcove floor plan

11/10/00 djt

Use recommended

floor protection

7/16” Durock®

(or equivalent)

spaced 1” off

wood studs on

noncombustible

spacers

ST502

Fig. 17 Floor plan. Sheetrock on front face butts to Durock®
(or equivalent) alcove lining.

ST503

Alcove side view

11/10/00 djt

Joist Shield

(Supplied

by Chimney

Manufac-

turer)

Metal

Stud

1” Air gap top

to bottom, on

both sides and

back wall

7/16” Durock®

(or equivalent)

Combustible

facing may

overlap metal

studs by 1”

ST503

Fig. 18 Alcove side section.