Asc-plus – Specialty Concepts ASC-Plus User Manual

Page 23

Advertising
background image

ASC-Plus

-

F I E L D T E S T P R O C E D U R E

The following is a field test procedure for the standard ASC-Plus charge controller. For
BENCH TESTING, substitute a properly current-limiting power supply for the array.

TEST 1: Alternate A ( Active solar array required )
This will test the basic operation of the ASC-Plus by testing the FET’s (not shorted or open).

Requirements: digital multi-meter (dmm)

active solar array, Voc at least 17 volts

1) Connect the array plus and minus wires to the appropriate terminals on the ASC-Plus

(no battery connection).

2) Measure voltage at BATT(+) and BATT(-) terminals on the ASC-Plus. The reading

should be between 14.0 and 15.0 volts. If this reading is very high, 16-20 volts,
or very low, 2-5 volts, the unit is defective.

TEST 1: Alternate B ( If no active solar array is available )
Tests for the most common failure condition: shorted FET’s. This problem would cause a “no

charging” condition.

Requirements: digital multi-meter (dmm)

1) Remove all connections from the ASC-Plus
2) Set multi-meter to the 200

resistance scale

3) Take measurements from ASC-Plus terminals. Contact positive lead of the meter to

ARRAY (+) and negative lead of meter to ARRAY (-). Reading should be open
(>200

). A short (<10

) indicates unit is defective.

TEST 2
This procedure tests the condition of the blocking diode.

Requirements: digital multi-meter (dmm)

1) Remove all connections from the ASC-Plus
2) Set multi-meter to the 2K

resistance scale

3) Take measurements from ASC-Plus terminals. Contact positive lead of the meter to

ARRAY (+) and negative lead of the meter to BATT (+). Reading should be less
than 2K

. Above 2K

would indicate a defective unit.

4) Reverse contacts (positive lead to BATT (+) and negative lead to ARRAY (+)).

Reading should be greater than 2K

. Below 2K

would indicate a defective unit.

Advertising