Fuse removal test – Specialty Concepts SC3/15 User Manual

Page 14

Advertising
background image

9. BAD CONNECTION: PANEL - The panel connection to the controller may be weak or completely

out. This may include problems with the connections at the SC3/15 (yellow wire and black wire),
both panel connections (“+” or “-”) or fuses and unsoldered crimp connectors in these lines. Also,
wire that is too small for the length of the run may cause a voltage drop. (See INSTALLATION
INSTRUCTIONS
, step #17. CHECK FOR VOLTAGE DROP.)

10. BAD CONNECTION: BATTERIES - The SC3/15 needs to read an accurate battery voltage to

regulate the charging correctly. The battery connection to the controller may be weak or completely
out. Connection problems can be with a blown or defective fuse, a bad fuse holder, the
connections at the SC3/15 (red wire and black wire), both battery terminals (“+” or “-”) or fuses and
unsoldered crimp connectors in these lines. Also, wire that is too small for the length of the run may
cause a voltage drop. (See INSTALLATION INSTRUCTIONS, step #17. CHECK FOR VOLTAGE
DROP
.)

11. CONTROLLER FUSE BLOWN - The fuse on the front panel of the controller can be blown and

need replacing. Replacement is a 15 amp AGC fuse. Before replacing a blown fuse, locate and
correct the cause. Possible causes for blown fuses:

1) Reverse battery connection

2) Incorrect connection

3) Array current is over 15 amps

12. INCORRECT CALIBRATION - The SC3/15 may be functional but the calibration of the voltage

set-point may be off. Rarely would the factory setting stray much unless there was a manual
adjustment to the backside components. All adjustments should be performed at the factory.

13. SYSTEM NOISE - The SC3/15 can be subjected to electrical noise from a converter or inverter.

This will cause the meter readings to be erratic and the light to turn on and off. If the SC3/15 is
connected to the converter, or to a buss that is connected to a converter, try connecting the
SC3/15 directly to the battery instead.

Fuse Removal Test

This test temporarily removes the battery connection to the SC3/15. By noting the reaction on the

SC3/15’s volt-meter, one can receive additional information about the workings of your system.

Requirements: - Perform this test at mid-day on a day with good sun. The battery voltage must

be over 10 volts.

First, observe "BATTERY VOLTAGE" reading.

Remove the fuse, observe the "BATTERY VOLTAGE" reading again. ( When the fuse is

removed, it is normal for the “CHARGING” light to go on and to hear a faint buzzing).

Note the new reading and any changes and refer to the sections below.

Remember to replace the fuse after testing.

VOLT METER MOVES TO EXTREME LEFT (“9” ON METER) - If the meter drops to “9” on meter,

this means that the array panel is bad or disconnected or the SC3/15 is defective.

METER STAYS THE SAME - If the meter stays the same, that means that the controller is not

connected to the battery.

THE METER MOVES TO THE RIGHT - This is the correct reaction and suggests the unit is working

properly. If it appears that the battery is overcharging, check the voltage directly at the

battery

with a volt-meter. A battery voltage of over 14.7 volts would indicate the controller was
defective or out of calibration.

HELP NOTES:

(Continued)

Advertising