8. WIRING

8.1. Connection Diagram

9P removable terminal

plug (accessory)

N-8000MI

Contact input signals

Contact output signals

To AC mains or a UPS

(Uninterruptible power supply)*

Note

If there is a danger of lightning

strikes, insert an appropriate

surge arrester into the power

line.

Be sure to ground this

terminal unless the unit

connects to a PBX.

1. Power supply connection

Connect the supplied power supply cord to AC

Mains or a UPS (Uninterruptible power supply).

About power supply cord handling

The supplied power supply cord is designed for

exclusive use with the N-8000MI.

Use the supplied power supply cord only with the

N-8000MI.

2. Contact input terminal connection

(Refer to p. 15, "Connector Connection.")

[Specification of no-voltage make contact input]

Short-circuit current: 10 mA

Open-circuit voltage: 12 V

3. Contact output terminal connection

Contact output terminals have no polarity.

(Refer to p. 15, "Connector Connection.")

[Specification of relay contact output]

Withstand voltage: 24 V DC

Control current: Max. 0.5 A

* Select an appropriate UPS taking into consideration the total power consumption of all system components

and the required backup time, and also the requirement that the UPS should employ the on-line power system.

Reference

Multi Inertface Unit: Maximum 19 W.

8-Port 10M/100M Switching Hub: 10 W (Differs depending on products.)