User manual, English, Rt9 ups – XMART Optima RT9 10K User Manual

Page 13: Isotx, Circuit breakers and wiring selection

Advertising
background image

User Manual

- ONLINE 6K/10K RACK-TOWER ISOTX UPS

ENGLISH

__________________________________________________________________________________________________________________________

www.xmart-ups.com

130717 RT9- 6K-10K (ENG)

- 13

CIRCUIT BREAKERS AND WIRING SELECTION


Breakers and Gauge of the wires used in the installation must be rated to drive current values in Amps as indicated in below tables.
NOTE every country has its local electrical requirements and regulations. If local electrical regulations require higher rates than
suggested values in this section, please follow local regulations.

RT9 UPS

INPUT 220Vac 1Ph

OUTPUT 220Vac 1Ph

EXT. BATT (240Vdc)

MODEL

BREAKER & WIRING

BREAKER & WIRING

BREAKER & WIRING

6KVA

Salida 220Vac

AC Breaker: 40A (Curve D)

Max. Nominal Current: 36A

Wiring (min. size):

10AWG (6 mm2)


AC Breaker: 40A (Curve D)

Max. Nominal Current: 36A

Wiring (min. size):

10AWG (6 mm2)


Breaker: 50A DC (Curve C)

Max. Nominal Current: 30A DC

Wiring (min. size):

10 AWG (6 mm2)

10KVA

Salida 220Vac

AC Breaker: 63A (Curve D)

Max. Nominal Current: 60A

Wiring (min. size):

8AWG (10 mm2)

AC Breaker: 63A (Curve D)

Max. Nominal Current: 60A

Wiring (min. size):

8AWG (10 mm2)

Breaker: 63A DC (Curve C)

Max. Nominal Current: 50A DC

Wiring (min. size):

8 AWG (10 mm2)

ISOTX

UNIQUE OUTPUT: 1 x 120Vac

(100% Watts)

SEPARE OUTPUTS: 2 x 120Vac

(50% Watts C/U)

6KVA con ISOTX

Output 110/220V

Unique Output Capacity: 6000VA / 5400W

Output Voltage: 120Vac

AC Breaker: 80A (Curve D)

Max. Nominal Current: 70A

Wiring (min. size): 6AWG (16 mm2)

VA/W per Output: 3000VA / 2700W

Output Voltage: 120Vac

AC Breaker: 40A (Curve D)

Max. Nominal Current: 36A

Wiring (min. size): 10AWG (6 mm2)

10KVA con ISOTX

Output 110/220V

Unique Output Capacity: 10000VA / 9000W

Output Voltage: 120Vac

AC Breaker: 125A (Curve D)

Max. Nominal Current: 120A

Wiring (min. size): 3AWG (35 mm2)

VA/W per Output: 5000VA / 4500W

Output Voltage: 120Vac

AC Breaker: 63A (Curve D)

Max. Nominal Current: 60A

Wiring (min. size): 8AWG (10 mm2)

Recommended cable size according to 1999 NEC based on 30ºC air ambient temperature for 4 copper cables in conduit.

WARNING: Above wire gauge values are only a recommendation.
The wire size is strongly affected by diverse factors such as: Operation temperature, wire length, type of wire and kind of
installation. Electrical contractor must assure an appropriate selection for wire and protection devices sizing for complying
with local regulations for electrical installations. Wiring colors must be selected according to local directives and
regulations


ADVERTENCIA: ISOTX module offers 2 separate outputs 120Vac L-N each. When outputs are used separately, each
output only can supply 50% of total UPS capacity. For example for 6KVA UPS, each separate output will supply 3KVA.
You can have one 120Vac output with 100% capacity by connecting 2 separate outputs in parallel.

Advertising
This manual is related to the following products: