User manual, English – XMART Optima RT9 10K User Manual

Page 4

Advertising
background image

User Manual

- ONLINE 6K/10K RACK-TOWER ISOTX UPS

ENGLISH

__________________________________________________________________________________________________________________________

www.xmart-ups.com

130717 RT9- 6K-10K (ENG)

- 4

To enlarge batteries life expectancy it is recommendable to fully discharge

UPS one every 2 to 3 months

During UPS storage recharge batteries according to the following table:

WARNING: BATTERIES MAINTENANCE

• Batteries capacity, in general (of all kinds), decrease with time and use.

• Our products contain high quality batteries only.

• Batteries useful life in our UPS is between 4 and 5 years, considering environment temperature under 25 ºC and optimal

operational conditions. This time can be dramatically reduced by high temperature and other adverse operation condition.

• Batteries life expectancy may be also affected by other operation conditions such as electrical service quality as well as

number and kind of equipments connected to UPS

• Batteries should be periodically tested to check capacity and assure and appropriate back up.





Storage Temperature

Recharging Frequency

Recharging Time

-25°C a +30°C

Every 4 months

During 6 hours

+30°C a +45°C

Every 2 months

During 6 hours

SAFETY STANDARDS

SAFETY:

IEC/EN 62040-1

EMI (Radiated):

IEC/EN 62040-2 (Cat 3)

EMI (Conducted):

IEC/EN 62040-2 (Cat 3)

EMS Power-Frequency Magnetic Field:

IEC/EN 61000-4-8 (Level 4)

EMS Low Freq. Signals:

IEC/EN 61000-2-2

EMS (ESD):

IEC/EN 61000-4-2 (Level 4)

EMS (RS):

IEC/EN 61000-4-3 (Level 3)

EMS (EFT):

IEC/EN 61000-4-4 (Level 4)

EMS (SURGE):

IEC/EN 61000-4-5 (Level 4)

EMS (CS):

IEC/EN 61000-4-6 (Level 3)

This product has been designed to operate in industrial and commercial applications. If it is used in different application some considerations for
avoiding interferences could be necessary.