User manual, English, Technical specifications – XMART Optima RT9 10K User Manual

Page 40

Advertising
background image

User Manual

- ONLINE 6K/10K RACK-TOWER ISOTX UPS

ENGLISH

__________________________________________________________________________________________________________________________

www.xmart-ups.com

130717 RT9- 6K-10K (ENG)

- 40

13.- TECHNICAL SPECIFICATIONS

ONLINE RT9 UPS

Capacity / Capacidad
Output PF / FP de Salida:
INPUT / ENTRADA
Input Voltage / Voltaje de Entrada

Input Range / Rango de Entrada

Frequency Range / Rango Frecuencia
Phase / Fases
Power Factor / Factor de Potencia
THDi
Slew Rate / Segumiento Frecuencia
OUTPUT / SALIDA

UPS
ISOTX (optional module)
Voltage Regulation / Regulación Salida
Frequency / Frecuencia (Batt. Mode)
Current Crest Ratio / Factor de Cresta

THDv

Transfer Times / Tiempos Transfer.
Waveform / Forma de Onda
Power Outlets / Salidas
OVERLOAD / SOBRECARGA

AC Mode / Modo Normal
Battery Mode / Modo Batería
EFFICIENCY / EFICIENCIA
Eco Mode / Modo ECO

AC Mode / Modo AC
Battery Mode / Modo Batería
BATTERIES / BATERIAS
Type and Qty / Tipo y Cantidad
Internal Batt. Pack / Bat. Internas
External Batt Cab. / Gab. Ext.
Typical Recharge T. / T. de Recarga
Internal Battery Pack / Bat. Internas
External batt cabinet / Gabinete Ext.
Charging Amps / Corriente de Carga
Charging Voltage / Voltaje Cargador

2.0 A (Max.)

273.0 VDC

12V/7AH x 20 pcs

12V/9AH x 20 pcs

3.5 H (90%)

4 H (90%)

12V/7AH x 20 pcs

12V/9AH x 20 pcs

88% / 84% (EX / ISO)

Separate Cabinet

6K-RT9

10K-RT9

6KVA / 5.400W

10KVA / 9.000W

Terminal Block / Regleta de Conexión

+/- 1% (Batt. Mode / Modo Batería)

50 Hz +/- 0.1 Hz / 60 Hz +/- 0.1 Hz

< 3% @ Linear Load / Carga Lineal

<4% @ No Linear Load / Carga no Lineal

3:1 @ 100% load.

90% / 86% (EX / ISO)

1 phase (L1-N1): 200/208/220/230/240Vac

Dual Isolated Outputs: 2 phases (L1-N1) + (L2-N2): 104/110/115/120Vac (L-N)

96% / 92% (EX / ISO)

Separate Cabinet

0 ms

Sine Wave / Sinusoidal Pura

220Vac (single phase: L-N + ground / L-N + Tierra)

Rated Input / Entrada Nominal: 208/220/230/240 Vac

(176Vac-300Vac) +/- 3% @ 100% load

(110Vac-300Vac) +/- 3% @ 50% load

40 - 70 Hz

1 Phase+Ground / 1 Fase+Tierra

> 0.99 @ 100%load

< 5% @ 100%load

1 Hz / s

0.9

0.9

100%~110%: 10m / 110%~130%: 1m / >130% : 1s

100%~110%: 30s / 110%~130%: 10s / >130% : 1s

Depending on external battery configuration (depende de cantidad de baterías externas)