Unit Sizes 5QBA028 thru 064 — Bearings are bolted

to an angle support fastened to fan scroll (Fig. 15).
To correct shaft and wheel concentric misalignment:

1. Loosen bearing support bolts and shim or move

as required.

2. Retighten bearing support bolts.

HORIZONTAL SHAFT ALIGNMENT (All units)
— If the shaft has moved and all wheels are off

horizontal center, recenter the shaft as follows:

1. Loosen the setscrews holding bearing locking

collar at each end of shaft (Fig. 14 or 15).

2. Slide shaft and wheel assembly horizontally until

wheels are horizontally centered (Fig. 11).

3. Slide the bearing locking collars against the bear­

ing race and turn in direction of shaft rotation
until tight.

4. Retighten locking collar setscrews.

CUTOFF CLEARANCE (Unit Sizes 044, 054 and
064) — After centering and aligning the fan wheel,
loosen cutoff sheet (Fig. 13), adjust for 1-1/4 in.
clearance as shown and then tighten securely.

FAN, PULLEY AND BELT ADJUSTMENT

Refer to the Service section entitled Indoor-Air

Fan Adjustment.

PILLOW BLOCK
FAN SHAFT
BEARING.

SHAFT EXTENSION
LONGER ON
ONE END TO

ACCOMMODATE
DRIVE PULLEY

BEARING LOCKING
COLLAR 2 SET SCREWS

'HOLLOW SHAFT

3 FANS ON 028-064

'SHIM IF NECESSARY

Fig. 15 — Horizontal Shaft Alignment

Step 9 — Install heating coil if supplied.

On 50BA,BB004 and 006 units, any water or

steam heating coil must be installed thru the back
of the unit as described in the Installation Instruc­
tions shipped with the accessory coil.

Step 10 — Install supply air (evaporator)
ductwork.

Connect supply ducts to flanges on air supply

opening (Fig. 1), using a flexible connection.

Attach ductwork to building structure and insu­

late with fiberglass and vapor barrier to prevent
sound transmission and vapor condensation.

Weatherproof external ductwork, joints and

openings with flashing and mastic in accordance
with applicable codes.

Ducts passing thru an unconditioned space must

be insulated and covered with a vapor barrier.

Step 11 — Install return air ductwork (004 —
012 units).

The unit back panel is stamped to indicate alter­

nate return air (or outdoor air inlet) opening as
indicated in Fig. 1.

1. Cut out the alternate return air opening as

required.

2. Attach a 1-in. flange to unit back panel or attach

a flanged, flexible duct connection directly to
unit as desired.

If an outdoor makeup air damper is to be in­

stalled, attach it directly to unit back panel and
install flexible connection between damper
assembly and remaining ductwork.

Use accepted ductwork installation procedures.
Follow all applicable codes.

3. Restrict or completely blank off the standard

return air opening with a field-fabricated filler
panel. This panel must be removable for service
access. Refer to Service section entitled Return
Air Grille Removal as required.

Step 12 — Check return-air filters.

Be sure filters shipped with unit are the correct

size (see Table 1). Never operate unit without return-

air filters in place.

Step 13 — Check compressor spring mounts

(50BB008 and 50BA,BB012 thru 064).

The compressors are held rigid in shipment by

bolts extending thru a washer, grommet and com­
pressor foot into a weld nut (for 064 unit, see para­
graph below).

Loosen each bolt (4 per compressor) until com­

pressor floats freely on springs. Then retighten bolts
until there is slight pressure on the neoprene gasket.
This will steady the compressor and prevent
start and stop rocking.

The 50BA,BB064 units are shipped with 4 special

flanged washers and neoprene grommets in a cloth
bag tied to the compressor. Remove the compressor
hold-down bolts. Then install the neoprene
grommets between the compressor feet and the

special washers. Reinstall the hold-down bolts and
tighten until there is slight pressure on the
grommets.

The compressors have reversible oil pumps that

operate in either direction; therefore the direction
of rotation need not be checked.
NOTE: Do not loosen bolts on 50BA008
compressor.

Step 14 — Make condenser connections.

WATER-COOLED (50BA) UNITS ^ GENERAL
— Condensers have water inlet and outlet connec­
tions as shown in Fig. 16. Piping arrangements for

city, waste or recirculating water are shown in

Fig. 17 thru 24.