Carrier 50BA User Manual

Page 15

Attention! The text in this document has been recognized automatically. To view the original document, you can use the "Original mode".

Advertising
background image

R£aRCUtAT{«6 SYBTeiiS - S£S NOTH )

NOTE For waste or city water, remove inlet manifold and supply

condensers individually

"Fig. 24 — 50BA064 Condenser Water Piping

50BA.BB*

COIL NO.

COMPR NO.

CONO NO.*

016

1

1

1

024,028,

034,064

1, 2

1, 2

1, 2

044,054

1, 2, 3

1,2,3

1, 2, 3

*50BB units are condenserless

Fig. 25 — Refrigeration Circuits (016-064)

Step 15 — Install unit drain line.

Install a trapped condensate drain line at unit

drain connection (Fig. 16). The drain requires
standard pipe connected to condensate pan nipple
as shown in Table 6. Figure 26 shows proper trap
design.

Determine design negative static pressure. This

pressure is not the same as fan total pressure, which
includes pressure losses downstream as well as
upstream from the indoor air fan. Always assume
the worst conditions, such as having return air filters
clogged with dirt.

Referring to Fig. 26, Differential 1 must be equal

to or larger than negative static pressure at design
operating conditions. Store enough water in trap to
prevent losing seal (Differential 2). This differential
must be equal to or larger than one-half the maxi­

mum negative static pressure. When the fan starts.

Differential 3 is equal to the maximum negative
static pressure.

Do not use drain line smaller than size listed in

Table 6. If required, cut hole in panel for drain line.

Pitch drain downward toward an open drain sump.
Provide a trap at least 3 in. high with plugged tee for

cleaning. Fill trap with water to make an air seal.
Observe all sanitary codes.

Table 6 — Condensate Drain Connections (in.)

UNIT SIZE

004,006,
008,012

016,024

028,034,
044,054

3/4

1

1-1/4

064

1

-

1/2

Fig. 26 — Condensate Drain

IS