-> Table 7 — Electrical Data

COMPRESSOR NO. 1

COMPRESSOR NO. 2

POWER SUPPLY

VULI-

IIMUUUK

UNIT

50BA.BB

VOLTS/PH/HZ

AGE

RANGE

RLA

LRA

RLA

LRA

FAN

MOTOR*

Min

Ckt

Ampst

MOCP

Ampst

Min

Max

BA

BB

BA

BB

BA

BB

BA

BB

Hp

FLA

BA

BB

BA

BB

230/1/60

207

253

19 8

19 8

88 0

88 0

_

_

_

_

1/3

33

28 1

28 1

45

45

004

208-230/3/60

187

253

13 0

13 0

87 0

87 0

_

1/3

3 3

19 6

19 6

30

30

460/3/60

414

528

5 5

5 5

30 0

30 0

1/3

0.8

7.7

7,7

15

15

230/1/60

207

264

27 9

39 0

106 0

135 0

__

3/4

5 3

40 2

54 1

70

90

006

208-230/3/60

187

253

18 3

20 6

105 0

136 0

--

3/4

7 1

30 0

32 9

45

50

460/3/60

414

528

88

104

35 0

49 0

_

_

3/4

7

6

12 6

14 6

20

25

575/3/60

518

632

64

84

27 0

41 0

_

_

3/4

1 1

9 1

11,6

15

25

208-230/3/60

187

253

23 7

31 3

184 0

137 0

_

_

_

1

40

33 7

44 0

50

70

008

460/3/60

414

506

11 4

14 1

69 0

62 0

_

1

1 6

15 9

194

25

30

575/3/60

518

632

96

11 3

55 0

50 0

1

1 4

134

15 5

20

25

208-230/3/60

187

253

36 3

40 0

137 0

170 0

_

_

2

60

52 0

56 0

80

90

012

460/3/60

414

506

14 6

180

62 0

77 0

2

2 8

21 1

25 9

35

40

575/3/60

518

632

11 4

14 4

50 0

62 0

2

23

16 6

20.7

25

35

208-230/3/60

187

253

50 0

64 0

191 0

266 0

--

2

70

70 0

87 0

110

150

016

460/3/60

414

506

22 1

29 0

86 0

120 0

2

3 1

31 0

40 0

50

50

575/3/60

518

632

17 9

23 0

69 0

96 0

~

2

2 5

25 0

32 0

40

35

208-230/3/60

187

253

36 0

45 0

1370

170 0

36 0

45 0

137 0

170 0

3

9 2

91 0

1110

125

150

024

460/3/60

414

506

16 0

20 0

62 0

77 0

160

20 0

62 0

77 0

3

46

40 8

49 8

50

60

575/3/60

518

632

12 9

16 0

50 0

62 0

129

16 0

50 0

62 0

3

3 4

32 9

40 0

45

45

208-230/3/60

187

253

49 3

64 0

191 0

266 0

35 7

45 0

137 0

170 0

5

16 2

1140

142 0

150

200

028

460/3/60

414

506

22 2

29 0

86 0

120 0

16 0

20 0

62 0

77 0

5

66

51 4

63 9

60

70

575/3/60

518

632

180

23 0

69 0

96,0

130

170

50,0

62.0

5

5,6

41.0

51.9

45

70

208-230/3/60

187

253

49 3

64 0

191 0

266 0

49 3

64 0

191 0

266 0

5

16 2

128 0

161 0

175

200

034

460/3/60

414

506

22 2

29 0

86 0

120 0

22 2

29 0

86 0

120 0

5

6 6

57 6

72 9

60

80

575/3/60

518

632

180

23 0

69 0

96 0

180

23 0

69 0

96 0

5

5 6

46.0

57 9

50

80

208-230/3/60

187

253

50 0

64 0

191 0

266 0

36 0

45 0

137 0

170 0

7-1/2

21 6

171 0

211 0

200

250

044t

460/3/60

414

506

23 0

29 0

86 0

120 0

160

20 0

62 0

77 0

7-1/2

9 5

77 0

95 0

90

110

575/3/60

518

632

180

69 0

130

50 0

7-1/2

8 4

62 5

80

208-230/3/60

187

253

50 0

64 0

191 0

266 0

50 0

64 0

191 0

266 0

10

28 0

191 0

236 0

225

300

054t

460/3/60

414

506

23 0

29 0

86 0

120 0

23 0

29 0

86 0

120 0

10

13 0

88 0

107 0

100

125

575/3/60

518

632

180

69 0

180

69 0

10

105

69 5

80

~

208-230/3/60

187

253

102 0

1190

506 0

506 0

102 0

119 0

506 0

506 0

15

46 2

276 0

314 0

350

400

064

460/3/60

414

506

50 0

50 0

253 0

253 0

50 0

50 0

253 0

253 0

15

21 0

134 0

134 0

175

175

575/3/60

518

632

38 0

50 0

176 0

176 0

38 0

50 0

176 0

176 0

15

16 4

102 0

129 0

125

175

FLA
Hp
LRA
MOCP
RLA

Full Load Amps
Horsepower
Locked Rotor Amps
Maximum Overcurrent Protective Device (See Note 1 )
Rated Load Amps

"Indoor fan motors are 3-phase motors of same voltage as unit except those

with FLA values in italics These motors are single-phase motors of same
voltage as unit

tMin Ckt Amps and MOCP Amps values per NEC (See Note 1 )
iUnits 50BA,BB044 and 054 have 3 compressors Compressor no 1 data

applies to Systems 1 and 2; compressor no 2 data applies to System 3

NOTES;

• 1 In compliance with NEC requirements for multimotor and combination

load equipment (NEC Articles 430 and 440}, the overcurrent protective
device for the unit shall be fuse only

2 Phase imbalance must not exceed 2%
3 Fan motor power wiring, circuit breakers and other electrical components

are sized to accommodate special motors on the 50BA,BB016,024,028
and 034 units

4 Wire sizing amps are a sum of 125% of the FLA for largest motor plus

100% of FLA for all other motors in the unit

5 Maximum instantaneous current flow during starting is the sum of the

LRA for last compressor to start plus the FLA for all other compressors
in the unit

Table 8 — Maximum Wire Sizes for

Terminal Block (AWG or MCM)*

VOLT/

PHASE

UNIT 50BA,BB

008

012

016

024

028,
034

044

054

064

BA 1 BB

BA

BB

BA

BB

208 230/3

00

00

00

00

350

0000 350

350

350

350

500

460/3

00

00

00

00

00

00 ÒÒÓ0

0000

0000

350

350

575/3

00

00

00

00

00

00 1 —

00

-

350

350

’Terminal block not supplied on 004 and 006 unit sizes Wire size to be selected per NEC and supply

wires to be connected to factory-supplied pigtail wire connectors

’Step 16 — Make electrical connections.

GENERAL — Provide an adequate fused dis­

connect switch per NEC within sight of the unit.

Provision for locking switch open (OFF) is ad­

visable to prevent power from being turned on when
unit is being serviced.

On 50BA,BB016 thru 064 size units, power may

be supplied thru a branch circuit. Branch circuit
protection is provided in these units by manual reset

circuit breakers. Branch circuit must be in accord­

ance with NEC or local code, whichever takes
precedence. Power supplied to auxiliary equipment,
such as fan motors for air-cooled condenser or for
cooling tower, must be run separately.

POWER WIRING — Conduit opening for 50BA,
BB004 thru 012 units is on left side of unit near

control box; for 50BA,BB016 thru 064 units, the

opening is on back of unit near control box.