FILTER SECTION OR COMBINATION MIXING
BOX AND FILTER SECTION (All sizes and
arrangements, high and low velocity) — Refer to
Fig. 11.

Fig. 11 — Assembly of Acœssory Filter Section or

Combination Mixing Box and Filter Section — (All
Sizes and Arrangements — High-and Low-Velocity)

1. Remove shipping skid.

2. Face air discharge side of accessory toward air

intake side of applicable accessory or cooling

coil section.

3. Fasten support legs to low-velocity filter sec­

tion or filter section of combination mixing
box and filter section (sizes 070 thru 120 only)
with two hex head cap screws, plain washers
and nuts per leg.

4. Fasten flange 1 to matching flange of applicable

accessory or cooling coil section with three

(sizes 070 thru 120) or seven (sizes 130 thru

140 — preheat coil section sizes 135 and 140

excluded) 3/8-16 x 3/4-in. hex head cap screws
and matching flange weld nuts.

5. Fasten flange 1 to matching flange of preheat

coil section (sizes 135 and 140) per preceding

steps 5a, 3b, and 3c (substitute flange 1 for
flange 2 in step 5a).

6. Fasten flange 5 to matching flange of applicable

accessory or cooling coil section as follows;

a. Fasten flange 5 (sizes 070 thru 120) with

three 3/8-16 X 3/4-in. hex head cap screws
and matching flange weld nuts.

b. Fasten flange 5 to matching flange of appli­

cable accessory or cooling coil section
(preheat coil and cooling coil sections,
sizes 135 and 140 excluded) with seven

3/8-16 X 1-in. hex head cap screws and
matching flange weld nuts.

c. Fasten flange 5 to matching flange of pre­

heat coil section (sizes 135 and 140) with
seven 3/8-16

X

1-in. hex head cap screws

and hex nuts.

d. Fasten flange 5 to matching flange of cool­

ing coil section (sizes 135 and 140) with
seven

4

/4-20

X

1/2-in. self-tapping screws

and matching flange engagement holes.

7. Fasten flanges 2 to matching flanges of appli­

cable accessory or cooling coil section with:

three (accessory or cooling coil section —

sizes 070 thru 120); five (accessory or cooling
coil section — size 130) ; five (accessory section
— sizes 135 and 140); or six (cooling coil sec­
tion — sizes 135 and 140) 3/8-16 xl-m. hex
head cap screws and hex nuts per two flanges.

8. Tighten all screws securely.

9. Install filter blankoff panels, evenly spaced in

filter tracks, when using high-velocity filters in
low-velocity filter sections or combination
mixing box and filter section to ensure uniform
air distribution.

ATOMIZING SPRAY AND STEAM GRID
HUMIDIFIERS — Normally shipped assembled in
unit. If a separate shipment is made, refer to
Installation Instructions provided with humidifier.

Unit Suspension and Mounting

1. Level unit after mounting to insure proper coil

and base pan drainage.

2. Rig and suspend base unit from same points per

Fig. 1. Note that unit sizes 130 and 140 must
be installed on a suspended platform.

3. Rig and suspend accessory combination mixing

box and filter section as follows:
a. Directly fastened to base unit — Rig and

suspend from two top corners on air-intake
end of accessory. Use one suspension rod
per comer.

b. Remote from base unit — Rig and suspend

from four top corners of accessory. Use one
suspension rod per corner.

VIBRATION ISOLATORS

1. Arrangement A (unit size 070 thru 140). A

minimum of six isolators should be installed for
proper support — one on each comer of coil
section and one on each comer of air discharge
side of fan section. Two additional isolators
may be installed on air-intake side of fan
section.

2. Arrangements B and D (unit sizes 070 thru

140) and all arrangements (unit sizes 040 thru

060) — Four isolators should be installed for

proper support.

3. Two isolators are required under combination

mixing box and filter section for floor mounting.

4. Vibration isolator hangers are required on combi­

nation mixing box and filter section for sus­
pended applications per preceding steps 2a and

2b, under “Unit Suspension and Mounting.”

£