SERVICE

Coil Removal

1. Disconnect piping.

2. Remove coil cover panel.
3. Remove air baffle from both ends of coil on

leaving air side.

4. Remove and discard coil shipping hold-down

bolts from both ends of coil.

5. SUde coil out of unit. Handle cooling coils with

coil face vertical. Handle heating coils with coil

face vertical or horizontal. Lift coils from four

suspension points at corners as close to tube
sheets as possible per Fig. 27.

6. Replace in reverse order.

Fig. 27 — Handling Coil with Face Vertical

Fan Section Access

— All fan section sides, front

and top panels may be removed. The panels to be
removed for fan access will depend on unit
location and the amount of access required. Refer
to Fig. 28.

After removing panels, store them properly to

avoid damage to insulation. Before entering fan
section, protect insulation by placing cardboard or
boards on bottom of fan section to serve as a
walkway.

Fan Shaft Bearing Replacement

1. Remove belt guard, belts, and sheave.

2. Loosen bearing locking collar setscrews.

3. Remove bearing hold-down bolts.

4.

Remove bearing and observe the following

precautions:
a.

Make certain fan shaft surface is clean

between bearing and end of shaft.

b. Block up fan shaft. Do not let fan shaft

drop on bearing support, or let fan wheel

twist or bind between sides of fan housing.

5. Install new bearing and tighten bearing locking

collar setscrews per Table 1 and Fig. 26.

6. Make certain fan wheel does not rub sides of

fan housing after installing new bearings.

7. Recoat fan shaft with a rust inhibitor.

8. Replace sheave, belts, and belt guard.

ЧОТГ "rfstv-fx, iiy x iW :}'

i-jy c ia '.'f'.x i

*>t,: r ги>'e ij-i y td '.z i ■ 'tf- ,.

Fig. 28 — Removable Panels for Access to

Fan Section

Fan Shaft Removal

1. Remove fan shaft bearings per Fan Bearing

Replacement.

2. Refer to Fan Section Access and remove panels.

3. Loosen fan wheel setscrews (sizes 040 thru 060)

or fan wheel clamps (sizes 070 thru 140).

4. Block up fan wheels within housings to prevent

dropping when shaft is removed.

5. Remove bearing plates and sUde shaft from

unit.

6. Replace shaft in reverse order and replace any

damaged internal insulation. Refer to Fig. 2 or
Table 4.