Fig. 19 — Cooling Coil Condensate Piping

Coil Removal and Reversing

1. Remove coil coverplate.

2. Remove air baffle from both ends of coil on

leaving air side.

3. Remove coil hold-down bolts from both ends

of coil.

4. Shde coil out of unit. Lift coils from suspension

points at four corners as close to tube sheets as
possible. Never lift from center. Handle cooling

coils with coil face vertical.

5. Reverse coil per Fig. 20.
6. Reverse steps 1 thru 4 to reinstall. Cooling and

hot water heating coils must be reinstalled so
refrigerant or chilled water supply enters on
air-leaving face of coil and returns on air­

entering face. Steam heating coils must be

installed with upper connection for supply and
lower for return. Supply connection has a

raised letter “S” on return-bend type steam

coils. Supply connection is larger than return

on nonfreeze type steam coils.

Fig. 20 — Coil Reversing

Duct Connections

— Make connections per

accepted design practices. Refer to Carrier System
Design Manual for details.

Motor and Drive

GENERAL

1. Excessive tipping will cause oil loss in sleeve

bearing motors. Follow motor manufacturer’s

recommendations.

2. Check job prints to determine correct motor

mounting position.

3. Drive package numbers are marked on drive

package and label on drive end of fan section.

4.

Required center-to-center distance (C/D) be­

tween fan and motor shafts is marked on fan
drive package.

5. Refer to Table 7 for motor base used on unit

sizes 070 thru 140. A single bracket is used
universally for unit sizes 040 thru 060. Motors
larger than 50 hp must not be mounted on unit.

Use field-provided, floor-mounted base under

unit and motor.

Table 7 — Motor Base Usage

(Unit Sizes 070 thru 140)

MTR BASE

PART NO.

HP

RANGE*

NEMA FRAME

SIZE RANGE

MOTOR BASE

CRADLE DIM. (in.)

39BA070-453

V

2

-

2

O

56-256T or
56-286U

16 Vs

X

20 V

4

39B A110-453

25-50

284T-326T or
324U-356U

23 V

4

X 26V

‘Corresponds to frame sizes for open dripproof 1750 rpm motors

only.

UNIT SIZES 040 THRU 060 - Refer to Fig. 21.

Fig. 21 — Motor Base (Unit Sizes 040 Thru 060)

1

2

.

Set motor mounting bracket position (min or
max) to provide required drive center-to-center
distance.
Install motor on motor mounting and adjusting
brackets with hardware from accessory drive

package.

3. Install adjusting screw, locknuts, and rubber

bumpers (shipped in cloth bag, taped to motor
base) on motor adjusting bracket. Save three
1 ¡4-20

X

1 ¡2-in. self-tapping screws for belt