*Use 230-vo)t controller with 200-,208- or 230-volt motors

Fig. 7 — Motormaster® Electrical Connections

Table 4 — Components Required for

MOTORMASTER Use

UNIT

MODEL

RUN

CAPACITOR

TRANS­

FORMER

MOTOR

38AD024

600

100

HC96LH020

HT01AH951
HT01AH959

HC46VL220or

HC46VL221

38AD028

38AD034

38AD044
38AB054

38AB064

38AB084

600

HC96LH030

HT01AH952

HC52TE230

100

HT01AH954

REFRIGERANT PIPING

Refrigerant Line Sizes

will depend on length of

piping required between condensing unit and evap­
orator. Consideration must be given to liquid lift

and to compressor oil return. Refer to Part 3 of
Carrier System Design Manual for line sizing
information and Fig. 8 for recommended piping

details.

Single Pumpout Control

— All units are factory

wired to operate on single pumpout control and
require a field-supplied liquid line solenoid valve,
sized for minimum pressure drop, to be installed
immediately ahead of each expansion valve. If unit
is to be used with a chiller, wiring modifications
may be necessary. Refer to 38AB Application
Data, Chilled Water Applications.

Refrigerant Drier and Moisture Indicator

— A

filter-drier(s) and a liquid-moisture indicator are
shipped with unit for field installation. Refer to
Fig. 9 for typical recommended piping arrange­
ments and to Table 5 for physical data on driers.

Receiver

— No receiver is provided with unit. It is

recommended that one not be used.

Piping Procedure

— Do not remove plastic dust

plugs from suction and liquid line stubs in com­
pressor compartment until piping connections are

ready to be made. Pass nitrogen or other inert gas
thru piping while brazing, to prevent formation of

copper oxide.

NOTES
1 Lower split first on, last off

2

D as used in 8D etc, indicates the pipe diameter size as a measure of length

3

TXVE indicates Thermostatic Expansion Valve Equalizer Connection

Fig. 8 — Typical Piping Connections for Face Split Coils

T7T